2.10 Troubleshooting Without Fault Display
144
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Causes
Possible Solutions
The motor torque is not sufficient.
Use a larger motor.
Note:
If these items are correct, the demand on the motor is more than the motor capacity:
•
Parameter settings are correct.
•
The drive does not detect
ov [Overvoltage]
.
The drive and motor system reached the torque limit.
•
Examine the values set in
L7-01 to L7-04 [Torque Limit]
and increase them if necessary.
Note:
If the torque limit is enabled, deceleration time can increase because the drive cannot output
more torque than the limit.
•
If
H3-02, H3-10, H3-06 = 10, 11, 12, 15 [MFAI Function Select = Torque Limit]
has been set,
examine the settings for the MFAIs.
•
Examine the values set in
H3-02, H3-10, and H3-06
.
•
Use
U1-13 to U1-15 [Terminal A1, A2, A3 Input Voltage]
to make sure that the analog input
values set to terminals A1, A2, and A3 are applicable.
The load is more than the internal torque limit as specified by the drive rated
current.
Replace the drive with a larger capacity model.
◆
There Is Audible Noise from the Drive or Motor Cables when You Energize the
Drive
Causes
Possible Solutions
The relay switching in the drive is making too much noise.
•
Use
C6-02 [Carrier Frequency Selection]
to decrease the carrier frequency.
•
Connect a noise filter to the input side of the drive power supply.
•
Connect a noise filter to the output side of the drive.
•
Isolate the control circuit wiring from the main circuit wiring.
•
Use a metal cable gland to wire the drive.
•
Shield the periphery of the drive with metal.
•
Make sure that the drive and motor are grounded correctly.
•
Make sure that ground faults have not occurred in the wiring or motor.
◆
The Ground Fault Circuit Interrupter (GFCI) Trips During Run
Causes
Possible Solutions
There is too much leakage current from the drive.
•
Increase the GFCI sensitivity or use GFCI with a higher threshold.
•
Use
C6-02 [Carrier Frequency Selection]
to decrease the carrier frequency.
•
Decrease the length of the cable used between the drive and the motor.
•
Install a noise filter or AC reactor on the output side of the drive. Set
C6-02 = 1 [2.0 kHz]
when
connecting an AC reactor.
•
Disable the internal EMC filter.
◆
Motor Rotation Causes Unexpected Audible Noise from Connected Machinery
Causes
Possible Solutions
The carrier frequency and the resonant frequency of the connected machinery
are the same.
•
Adjust
C6-02 to C6-05 [Carrier Frequency]
.
•
Set
C6-02 = 1 to 6 [Carrier Frequency Selection = Frequency other than Swing PWM]
.
Note:
If
C6-02 = 7 to A [Carrier Frequency Selection = Swing PWM]
, the drive will not know if the
noise comes from the drive or the machine.
The drive output frequency and the resonant frequency of the connected
machinery are the same.
•
Adjust
d3-01 to d3-04 [Jump Frequency]
.
•
Put the motor on a rubber pad to decrease vibration.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...