Code
Name
Causes
Possible Solutions
LT-1
Cooling Fan Maintenance Time
The cooling fan is at 90% of its expected performance
life.
1.
Replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the
cooling fan operation time.
Note:
When the estimated performance life is expired, the terminal set to
H2-01 to H2-03 = 2F [MFDO Function Selection = Maintenance Notification]
will activate.
Code
Name
Causes
Possible Solutions
LT-2
Capacitor Maintenance Time
The capacitors for the main circuit and control circuit
are at 90% of expected performance life.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
When the estimated performance life is expired, the terminal assigned to
H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification]
will be ON.
Code
Name
Causes
Possible Solutions
LT-3
SoftChargeBypassRelay MainteTime
The soft charge bypass relay is at 90% of its expected
performance life.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
When the estimated performance life is expired, the terminal assigned to
H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification]
will be ON.
Code
Name
Causes
Possible Solutions
LT-4
IGBT Maintenance Time (50%)
The IGBT is at 50% of its expected performance life.
Check the load, carrier frequency, and output frequency.
Note:
When the estimated performance life is expired, the terminal assigned to
H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification]
will be ON.
Code
Name
Causes
Possible Solutions
oH
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature is more than the
L8-02 [Overheat Alarm
Level]
.
•
Measure the ambient temperature.
•
Increase the airflow around the drive.
•
Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
•
Remove objects near the drive that are producing too much heat.
There is not sufficient airflow around the drive.
•
Give the drive the correct installation space as shown in the
manual.
•
Make sure that there is sufficient circulation around the control
panel.
•
Examine the drive for dust or other unwanted materials that
could clog the cooling fan.
•
Remove unwanted materials that prevent air circulation.
The internal cooling fan or fans have stopped.
1.
Use the procedures in this manual to replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the
cooling fan operation time.
Note:
•
The drive detects this error if the heatsink temperature of the drive is more than
L8-02
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
Set the stopping method for this fault in
L8-03 [Overheat Pre-Alarm Selection]
.
Code
Name
Causes
Possible Solutions
oH2
External Overheat (H1-XX=B)
An external device sent an
oH2
.
1.
Find the external device that output the overheat alarm.
2.
Remove the cause of the problem.
3.
Clear the
Overheat Alarm (oH2) [H1-xx = B]
that was set to
MFDI terminals S1 to S6.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-02 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
oH3
Motor Overheat (PTC Input)
The thermistor wiring that detects motor temperature
is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...