L5-02: Fault Contact at Restart Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-02
(049F)
Fault Contact at
Restart Select
Sets the function that sends signals to the MFDO terminal set for
Fault [H2-
xx = E]
while the drive is automatically restarting.
0
(0, 1)
0 : Active Only when Not Restarting
1 : Always Active
■
L5-04: Interval Method Restart Time
No.
(Hex.)
Name
Description
Default
(Range)
L5-04
(046C)
Interval Method
Restart Time
Sets the time interval between each Auto Restart attempt. Set
L5-05 = 1
[Auto-Restart Method = Continuous/Immediate Attempts]
to enable this
function.
10.0 s
(0.5 - 600.0 s)
■
L5-05: Auto-Restart Method
No.
(Hex.)
Name
Description
Default
(Range)
L5-05
(0467)
Auto-Restart Method
Sets the count method for the Auto Restart operation.
0
(0, 1)
0 : Continuous/Immediate Attempts
Counts the number of successful fault resets through Auto Restart.
When this value >
L5-01
, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
1 : Interval/Attempt after L5-04 sec
Counts the number of successful and unsuccessful fault resets through Auto Restart. The drive does the Auto
Restart process again in the intervals set in
L5-04 [Interval Method Restart Time]
.
When this value >
L5-01
, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
■
L5-07: Fault Reset Enable Select Grp1
No.
(Hex.)
Name
Description
Default
(Range)
L5-07
(0B2A)
Fault Reset Enable
Select Grp1
Use these 4 digits to set the Auto Restart function for
oL1
to
oL4
. From left
to right, the digits set
oL1
,
oL2
,
oL3
, and
oL4
, in order.
1111
(0000 - 1111)
0 : Disabled
1 : Enabled(—/—/—/oL4)
Figure 11.141 Setting Digits and Fault Code
■
L5-08: Fault Reset Enable Select Grp2
No.
(Hex.)
Name
Description
Default
(Range)
L5-08
(0B2B)
Fault Reset Enable
Select Grp2
Use these 4 digits to set the Auto Restart function for
Uv1
,
ov
,
oH1
, and
GF
.
From left to right, the digits set
Uv1
,
ov
,
oH1
, and
GF
, in order.
1111
(0000 - 1111)
0 : Disabled
1 : Enabled(—/–/—/GF)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV