1.13 o: Keypad-Related Settings
YASKAWA
TOEPYAIGA5002A GA500 Programming
85
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o1-56
(11EF)
RUN
Analog Gauge Area
Setting
Sets the value used to display the monitor set in
o1-24 [Custom Monitor 1]
as an analog
meter. This parameter is only available when using an LCD keypad.
100.0%
(0.0 - 100.0%)
o1-58
(3125)
Motor Power Unit
Selection
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
1
(0, 1)
◆
o2: Keypad Operation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets you use
to switch between LOCAL and REMOTE
Modes.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-02
(0506)
STOP Key Function
Selection
Sets the function to use
on the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
o2-05
(0509)
Home Mode Freq Ref
Entry Mode
Sets the function that makes it necessary to push
to use the keypad to change the
frequency reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
0
(0, 1)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from
the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-07
(0527)
Keypad RUN Direction
@ Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0 : Forward
1 : Reverse
0
(0, 1)
o2-09
(050D)
Reserved
-
-
o2-19
(061F)
Expert
Parameter Write during
Uv
Lets you change parameters during
Uv [Undervoltage]
.
0 : Disable
1 : Enabled
0
( 0, 1 )
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disable
1 : Enabled
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...