T2-10: PM Motor Stator Resistance
No.
(Hex.)
Name
Description
Default
(Range)
T2-10
(0754)
PM Motor Stator Resistance
Sets the stator resistance for each motor phase.
Determined by T2-02
(0.000 - 65.000 Ω)
Note:
This parameter does not set line-to-line resistance.
■
T2-11: PM Motor d-Axis Inductance
No.
(Hex.)
Name
Description
Default
(Range)
T2-11
(0735)
PM Motor d-Axis
Inductance
Sets the d-axis inductance of the motor on a per phase basis.
Determined by T2-02
(0.00 - 600.00 mH)
■
T2-12: PM Motor q-Axis Inductance
No.
(Hex.)
Name
Description
Default
(Range)
T2-12
(0736)
PM Motor q-Axis
Inductance
Sets the q-Axis inductance of the motor on a per phase basis.
Determined by T2-02
(0.00 - 600.00 mH)
■
T2-13: Back-EMF Units Selection
No.
(Hex.)
Name
Description
Default
(Range)
T2-13
(0755)
Back-EMF Units Selection
Sets the units that the drive uses to set the induced voltage constant.
0
(0, 1)
0 : mV/(rev/min)
1 : mV/(rad/s)
Note:
•
When
T2-13 = 0
, the drive will use
E5-24 [PM Back-EMF L-L Vrms (mV/rpm)]
and will automatically set
E5-09 [PM Back-EMF Vpeak
(mV/(rad/s))] = 0.0
.
•
When
T2-13 = 1
, the drive will use
E5-09
and will automatically set
E5-24 = 0.0
.
■
T2-14: Back-EMF Voltage Constant (Ke)
No.
(Hex.)
Name
Description
Default
(Range)
T2-14
(0737)
Back-EMF Voltage Constant
(Ke)
Sets the motor induced voltage constant (Ke).
Determined by T2-13
(0.0 - 2000.0)
■
T2-15: Pull-In Current Level
No.
(Hex.)
Name
Description
Default
(Range)
T2-15
(0756)
Pull-In Current Level
Sets the level of the pull-in current as a percentage of
E5-03 [PM Motor Rated Current (FLA)]
.
Usually it is not necessary to change this setting.
30%
(0 - 120%)
If the load inertia is high, increase the setting value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...