YASKAWA
TOEPYAIGA5002A GA500 Programming
401
When the output current decreases to the software current limit level, the drive starts usual operation.
■
L8-19: Freq Reduction @ oH Pre-Alarm
No.
(Hex.)
Name
Description
Default
(Range)
L8-19
(04BF)
Freq Reduction @ oH Pre-
Alarm
Sets the ratio at which the drive derates the frequency reference during an
oH
alarm.
0.8
(0.1 - 0.9)
When these two conditions are correct, this function is enabled:
•
L8-03 = 4 [Overheat Pre-Alarm Ope Selection = Run@L8-19 Rate]
•
oH
alarm is output
■
L8-27: Overcurrent Detection Gain
No.
(Hex.)
Name
Description
Default
(Range)
L8-27
(04DD)
Overcurrent Detection Gain
Sets the PM motor overcurrent detection level as a percentage of the motor rated current value.
300.0%
(0.0 - 1000.0%)
Note:
•
If the setting value for
L8-27
is the same or almost the same as the setting value for
L7-xx [Torque Limit]
, the drive can detect
oC2
[Overcurrent2]
.
•
On drives with software versions PRG:1022 and later, this function is disabled when you set
L8-27 = 0.0
. Under usual circumstances, do
not set
L8-27 = 0.0
. The
“
PRG
”
column on the nameplate on the right side of the drive identifies the software version. You can also use
U1-
25 [Software Number]
to identify the software version.
•
If the drive rated current is much higher than the motor rated current, PM motor magnets can demagnetize when current flows at the drive
overcurrent detection level. When you set a low overcurrent detection level to prevent PM motor demagnetization, make sure that you
adjust
L8-27
.
■
L8-29: Output Unbalance Detection Sel
No.
(Hex.)
Name
Description
Default
(Range)
L8-29
(04DF)
Output Unbalance Detection
Sel
Sets the function to detect
LF2
.
1
(0, 1)
This function prevents damage to PM motors. Current unbalance can heat a PM motor and demagnetize the magnets.
When the current is unbalanced, the drive will detect
LF2
to stop the motor and prevent damage to the motor.
0 : Disabled
1 : Enabled
■
L8-31: LF2 Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-31
(04E1)
LF2 Detection Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1
–
100)
When the output current is unbalanced for longer than the time set in
L8-31
, the drive detects
LF2
.
Note:
•
Set
L8-29 = 1 [Output Unbalance Detection Sel = Enabled]
to enable
L8-31
.
•
If the drive incorrectly detects
LF2
, increase
L8-31
in 5-unit increments.
•
The keypad shows
L8-31
when
E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)]
in EZ Vector Control.
■
L8-35: Installation Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
0
(0 - 3)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...