The run command is not input
•
The output current is less than 30% of the drive rated current.
■
L8-07: Output Phase Loss Protection Sel
No.
(Hex.)
Name
Description
Default
(Range)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
1
(0 - 2)
Note:
The drive can incorrectly start output phase loss detection in these conditions:
•
The motor rated current is very small compared to the drive rating.
•
The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
If the drive loses one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
2 : Fault when two phases are lost
If the drive loses more than one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
■
L8-09: Output Ground Fault Detection
No.
(Hex.)
Name
Description
Default
(Range)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
Determined by o2-04
(0, 1)
0 : Disable
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect
GF [Ground
Fault]
.
Note:
If the ground path impedance is low, the drive can detect
oC [Overcurrent]
,
SC [Out Short Circuit or IGBT Fault]
, or
ov [DC Bus
Overvoltage]
instead of
GF
.
■
L8-10: Heatsink Fan Operation Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0
(0 - 2)
0 : During Run, w/ L8-11 Off-Delay
The drive turns on the fan when a Run command is active.
1 : Always On
The fan turns on when you supply power to the drive. When you release the Run command and the delay time set in
L8-11 [HeatsinkCoolingFan Off DelayTime]
is expired, the fan stops. his setting extends the fan lifetime.
2 : On when Drive Temp Reaches L8-64
The fan turns on when the drive detects that the main circuit is overheating.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...