TOEPYAIGA5002A GA500 Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
◆
C3: Slip Compensation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C3-01
(020F)
RUN
Slip Compensation Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this
setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
•
E2-01 [Motor Rated Current (FLA)]
•
E2-02 [Motor Rated Slip]
•
E2-03 [Motor No-Load Current]
Determined by A1-02
(0.0 - 2.5)
C3-02
(0210)
RUN
Slip Compensation Delay
Time
Sets the slip compensation delay time when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
Determined by A1-02
(0 - 10000 ms)
C3-03
(0211)
Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated
slip.
200%
(0 - 250%)
C3-04
(0212)
Slip Compensation at
Regen
Sets the slip compensation function during regenerative operation.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
0
(0 - 2)
C3-05
(0213)
Output Voltage Limit
Selection
Sets the automatic reduction of motor magnetic flux when the output voltage is saturated.
0 : Disabled
1 : Enabled
0
(0, 1)
C3-16
(0261)
Expert
Vout Modulation Limit
Start Lvl
Sets the modulation factor that starts the output voltage limit operation when
C3-05 = 1
[Output Voltage Limit Selection = Enabled]
.
90.0%
(70.0 - 90.0%)
C3-17
(0262)
Expert
Vout Modulation Limit
Max Level
Sets the modulation factor used with
C3-18 [Output Voltage Limit Level]
for the output
voltage limit operation when
C3-05 = 1 [Output Voltage Limit Selection = Enabled]
.
100.0%
(85.0 - 100.0%)
C3-18
(0263)
Expert
Output Voltage Limit
Level
Sets the maximum drop width of the voltage reference when
C3-05 = 1 [Output Voltage
Limit Selection = Enabled]
.
90.0%
(50.0 - 100.0%)
C3-21
(033E)
RUN
Motor 2 Slip
Compensation Gain
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to
change this setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
•
E4-01 [Motor 2 Rated Current]
•
E4-02 [Motor 2 Rated Slip]
•
E4-03 [Motor 2 Rated No-Load Current]
Determined by E3-01
(0.0 - 2.5)
C3-22
(0241)
RUN
Motor 2 Slip Comp Delay
Time
Sets the slip compensation delay time for motor 2 when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
Determined by E3-01
(0 - 10000 ms)
C3-23
(0242)
Motor 2 Slip
Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor 2 rated
slip.
200%
(0 - 250%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...