1.3 Parameter Table
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
79
U1-49
(30C0H)
Output
Zero-phase
Voltage
Displays the detected zero-phase voltage at the output side.
10 V: Drive
rated voltage
1 V
–
U1-52
(1081H)
Output Voltage
Displays the detected output voltage value.
10 V: Drive
rated voltage
1 V
–
U1-54
(1083H)
Input Voltage
Displays the detected input voltage value (compatible with option cards).
10 V: Input
reference
voltage (o2-11)
1 V
–
U1-55
(1084H)
Input Current
Displays the detected input current value (compatible with option cards).
10 V: Drive
rated current
0.1 A
–
U2: Fault Trace
U2-01
(80H)
Current Fault
Displays the current fault.
No signal output
available
–
–
U2-02
(81H)
Previous Fault
Displays the previous fault.
No signal output
available
–
–
U2-03
(82H)
Frequency
Reference at
Previous Fault
Displays the frequency reference at the previous fault.
No signal output
available
0.01 Hz
–
U2-04
(83H)
Output
Frequency at
Previous Fault
Displays the output frequency at the previous fault.
No signal output
available
0.01 Hz
–
U2-05
(84H)
Output Current
at Previous Fault Displays the output current at the previous fault.
No signal output
available
0.1 A
–
U2-06
(85H)
Motor Speed at
Previous Fault
Displays the motor speed at the previous fault.
No signal output
available
0.01 Hz
–
U2-07
(86H)
Output Voltage at
Previous Fault
Displays the output voltage at the previous fault.
No signal output
available
1 V
–
U2-08
(87H)
DC Bus Voltage
at Previous Fault Displays the DC bus voltage at the previous fault.
No signal output
available
1 V
–
U2-09
(88H)
Output Power at
Previous Fault
Displays the output power at the previous fault.
No signal output
available
1 kW
–
U2-10
(89H)
Torque
Reference at
Previous Fault
Displays the torque reference at the previous fault.
No signal output
available
0.1%
–
U2-11
(8AH)
Input Terminal
Status at
Previous Fault
Displays the input terminal status at the previous fault. Displays the same
status as U1-10.
No signal output
available
–
–
U2-12
(8BH)
Output Terminal
Status at
Previous Fault
Displays the output terminal status at the previous fault. Displays the same
status as U1-11.
No signal output
available
–
–
U2-13
(8CH)
Drive Operation
Status at
Previous Fault
Displays the operation status of the drive at the previous fault. Displays
the same status as U1-12.
No signal output
available
–
–
U2-14
(8DH)
Cumulative
Operation Time
at Previous Fault Displays the cumulative operation time at the previous fault.
No signal output
available
1 h
–
U2-15
(7E0H)
Soft Starter
Speed Reference
at Previous Fault Displays the speed reference for the soft starter at the previous fault.
No signal output
available
0.01 Hz
–
U2-16
(7E1H)
Motor q-Axis
Current at
Previous Fault
Displays the q-axis current for the motor at the previous fault.
No signal output
available
0.1%
–
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 79 ページ 2013年10月11日 金曜日 午後8時18分