1.3 Parameter Table
66
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
L4-06
(4C2H)
Frequency
Reference at
Reference Loss
Sets the percentage of the frequency reference that the drive should run with
when the frequency reference is lost.
Default: 80%
Min: 0.0%
Max: 100.0%
L4-07
(470H)
Speed Agreement
Detection Selection 0: No detection during baseblock.
1: Detection always enabled.
Default: 0
Min: 0
Max: 1
L5: Fault Restart
L5-01
(49EH)
Number of Auto
Restart Attempts
Sets the number of times the drive may attempt to restart after faults occur.
Default: 0
Min: 0
Max: 10
L5-02
(49FH)
Auto Restart Fault
Output Operation
Selection
0: Fault output not active.
1: Fault output active during restart attempt.
Default: 0
Min: 0
Max: 1
L5-04
(46CH)
Fault Reset Interval
Time
Sets the amount of time to wait between performing fault restarts.
Default: 10.0 s
Min: 0.5 s
Max: 600.0 s
L5-05
(467H)
Fault Reset
Operation Selection
0: Continuously attempt to restart while incrementing restart counter only at
a successful restarts.
1: Attempt to restart with the interval time set in L5-04 and increment the
restart counter with each attempt.
Default: 0
Min: 0
Max: 1
L6: Torque Detection
L6-01
(4A1H)
Torque Detection
Selection 1
0: Disabled
1: oL3 detection only active during speed agree, operation continues after
detection
2: oL3 detection always active during run, operation continues after
detection
3: oL3 detection only active during speed agree, output shuts down on an
oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after
detection
6: UL3 detection always active during run, operation continues after
detection
7: UL3 detection only active during speed agree, output shuts down on an
oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3
fault
Default: 0
Min: 0
Max: 8
L6-02
(4A2H)
Torque Detection
Level 1
Sets the overtorque and undertorque detection level.
For V/f control, set the level as a percentage of the drive rated output current.
For Vector control, set the level as a percentage of the motor rated torque.
Default: 150%
Min: 0%
Max: 300%
L6-03
(4A3H)
Torque Detection
Time 1
Sets the time an overtorque or undertorque condition must exist to trigger
torque detection 1.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
No.
(Addr.)
Name
Description
Setting
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 66 ページ 2013年10月11日 金曜日 午後8時18分