9.2 Monitoring SERVOPACK Status
9.2.3 I/O Signal Monitor
9-5
9
Monitoring
9.2.3
I/O Signal Monitor
Use the following procedure to check I/O signals.
1.
Select
Monitor - Check Wiring
from the menu bar of the Main Window of the Sig-
maWin+.
2.
Click the
Monitor Mode
Button.
You can also use the above window to check wiring.
•
Checking Input Signal Wiring
Change the signal status at the host controller. If the input signal status on the window
changes accordingly, then the wiring is correct.
•
Checking Output Signal Wiring
Click the
Force Output Mode
Button. This will force the output signal status to change. If
the signal status at the host controller changes accordingly, then the wiring is correct.
You cannot use the
Force Output Mode
Button in the SERVO ON state.
Input signal status
Output signal status
Information