10 Input Assemblies (Drive Produces)
48
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
Standard Status 2 (Vendor Specific YE Assy) -152 (0x98)
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
OPE
OPE Fault
0: No OPExx Fault
1: OPExx
UV
Under Voltage
0: No Under Voltage
1: Under Voltage
Local/Remote
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output
Terminal M1/M2
0: Terminal M1/M2 OFF
1: Terminal M1/M2 ON
Multi-Function Photo Coupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Multi-Function Photo Coupler 2
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
Output Frequency
Actual Drive Speed
Monitors drive output frequency
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Actual Torque
Output Torque
Shows the torque reference.
Value displays in 0.1% units.
Actual Current
Actual Output Current
Monitors drive output current
Unit is 0.01 A for drives set up to 11 kW in Heavy Duty or Normal Duty and 0.1 A for drives set up for 15
kW and above.
Unit is not affected by Current Scale CS.
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
152
0
FAULT
ALARM
READY
Speed
Agree
Reset
REV
Running
ZSP
Running
1
–
–
Multi-
Function
Photo Coupler
2
Multi-
Function
Photo Coupler
1
Multi-
Function
Digital Output
Local/
Remote
UV
OPE
2
Output Frequency (Low Byte)
3
Output Frequency (High Byte)
4
Speed Reference (Low Byte)
5
Speed Reference (High Byte)
6
Actual Current (Low Byte)
7
Actual Current (High Byte)
Parameter
Data