722
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
52: Warning Signal
Setting Value
Function
Description
52
Warning Signal
The terminal activates when the number of starts is at the detection level.
■
60: Internal Cooling Fan Failure
Setting Value
Function
Description
60
Internal Cooling Fan
Failure
The terminal activates when the drive detects a cooling fan failure in the drive.
■
62: Modbus Reg 1 Status Satisfied
Setting Value
Function
Description
62
Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by
H2-08 [Modbus Register 1 Bit Select]
for the MEMOBUS register address set
with
H2-07 [Modbus Register 1 Address Select]
activates.
■
63: Modbus Reg 2 Status Satisfied
Setting Value
Function
Description
63
Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by
H2-10 [Modbus Register 2 Bit Select]
for the MEMOBUS register address set
with
H2-09 [Modbus Register 2 Address Select]
activates.
■
66: Comparator1
Setting Value
Function
Description
66
Comparator1
The terminal activates if the monitor value set with
H2-20 [Comparator 1 Monitor Selection]
is in range of the values of
H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit]
for the time set in
H2-24 [Comparator 1 On-Delay
Time]
.
A - H2-24
[Comparator 1 On-Delay Time]
B - H2-25
[Comparator 1 Off-Delay Time]
Figure 11.69 Comparator 1 Output Time Chart
Note:
The drive compares the monitors set with
H2-20
as absolute values.
■
67: Comparator2
Setting Value
Function
Description
67
Comparator2
The terminal activates if the monitor value set with
H2-26 [Comparator 2 Monitor Selection]
is not in the range of the values of
H2-27 [Comparator 2 Lower Limit]
and
H2-28 [Comparator 2 Upper Limit]
for the time set in
H2-30 [Comparator 2 On-
Delay Time]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...