YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
711
■
H2-69: Digital Output4 Secondary Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-69
(1B4F)
Expert
Digital Output4 Secondary
Func
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the
terminals assigned to functions by
H2-04 [Terminal P2-C2 Function Select]
.
F
(0 - FF)
■
H2-70: DigitalOutput4 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-70
(11F9)
Expert
DigitalOutput4 Logical
Operation
Sets the logical operation for the functions set in
H2-04 [Terminal P1-C1 Function Select]
and
H2-69 [Digital Output4 Secondary Func]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 703
for more information about the relationship between parameter
settings and logical operations.
■
H2-71: Digital Output 4 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-71
(11FA)
Expert
Digital Output 4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal P1-C1.
0.1 s
(0.0 - 25.0 s)
■
H2-72: Digital Output 5 Secondary Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-72
(11FB)
Expert
Digital Output 5 Secondary
Func
Sets the second function for terminal P2-C2. The logical calculation results of the terminals
assigned to functions by
H2-05 [Term P2-C2 Function Selection]
is output.
F
(0 - FF)
■
H2-73: DigitalOutput5 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-73
(11FC)
Expert
DigitalOutput5 Logical
Operation
Sets the logical operation for the functions set in
H2-05 [Term P2-C2 Function Selection]
and
H2-
72 [Digital Output 5 Secondary Func]
.
0
(0 - 8)
■
H2-74: Digital Output 5 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-74
(11FD)
Expert
Digital Output 5 Delay
Time
Sets the minimum ON time used to output the logical calculation results from terminal P2-C2.
0.1 s
(0.0 - 25.0 s)
◆
MFDO Setting Values
Selects the function configured to MFDO.
■
0: During Run
Setting Value
Function
Description
0
During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...