3.10 Crane Application Setup Procedure
224
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Note:
If the resulting frequency reference after having been multiplied by the gain of
S2-16
or
S2-17
is less than the frequency reference lower
limit, this lower limit value will be used. The frequency reference lower limit is the maximum setting value for the following
parameters.
•
d2-02 [Frequency Reference Lower Limit]
•
S1-01 [Brake Release Frequency(FWD)]
•
S1-02 [Brake Release Frequency(REV)]
•
S1-12 [Brake Hold Frequency (FWD)]
•
S1-13 [Brake Hold Frequency (REV)]
■
MFDI
H1-xx
Setting
Name
Description
3A
Micro Speed Gain1
When the corresponding terminal is on, the frequency reference is multiplied by the gain set to
S2-16 [Micro Speed Gain1]
.
3B
Micro Speed Gain2
When the corresponding terminal is on, the frequency reference is multiplied by the gain set to
S2-17 [Micro Speed Gain2]
.
Note:
When the frequency reduction gain 1 input is on, the gain set to
S2-16 [Micro Speed Gain1]
has priority.
■
Description of Operation
◆
Rapid Deceleration Function
The deceleration rate can be changed to rapidly stop operation by inputting a Run command in reverse to the
current running direction during the ramp to stop operation. This enables quick deceleration near the target
location even when using high-speed operation.
■
Description of Operation
Set
S2-18 = 1 [Rapid Deceleration Selection = Enabled]
to enable this function.
When deceleration starts after the Run command is turned off, and a Run command in reverse to the current
direction of motor rotation is input, the motor rapidly decelerates per the time set to
S2-19 [Rapid Deceleration
Time]
. When the Run command is turned off during rapid deceleration, rapid deceleration is turned off, and the
motor continues to decelerate at the selected normal deceleration rate.
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...