It is recommended to externally protect the electronic power supply for CPU and SLIO
bus with a 3A fuse (fast) respectively by a line circuit breaker 3A characteristics Z.
n
The power section supply of the internal I/Os is to be externally protected with a 6A
fuse (fast) respectively by a line circuit breaker 6A characteristics Z!
n
The power section supply of the SLIO bus is to be externally protected with a 6A fuse
(fast) respectively by a line circuit breaker 6A characteristics Z!
After PowerON of the System SLIO the LEDs RUN respectively MF get on so far as the
sum current does not exceed 1A. With a sum current greater than 1A the LEDs may not
be activated. Here the power module with the order number 007-1AB10 is to be placed
between the peripheral modules.
1
Shield bus carrier
2
Shield bus (10mm x 3mm)
3
Shield clamp
4
Cable shield
To attach the shield the mounting of shield bus carriers are necessary. The shield bus
carrier (available as accessory) serves to carry the shield bus to connect cable shields.
1.
Each System SLIO module has a carrier hole for the shield bus carrier. Push the
shield bus carrier, until they engage into the module. With a flat mounting rail for
adaptation to a flat mounting rail you may remove the spacer of the shield bus car-
rier.
2.
Put your shield bus into the shield bus carrier.
3.
Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
2.5.2 Wiring periphery modules
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal module!
Fusing
State of the electronic
power supply via LEDs
Shield attachment
Terminal module terminals
VIPA System SLIO
Basics and mounting
Wiring > Wiring periphery modules
HB300 | CPU | 013-CCF0R00 | en | 16-40