YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
75
Table 10.4 Multi-function Input Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
MFDI
S1
MFDI selection 1
(ON: Forward run, OFF: Stop)
•
Photocoupler
•
24 V, 6 mA
Note:
To set the MFDI power supply (Sinking/
Sourcing Mode or internal/external
power supply), install or remove a
jumper between terminals SC-SP or SC-
SN depending on the application.
•
Sinking Mode, Internal power supply:
Install the jumper to close the circuit
between terminals SC-SP.
NOTICE
Damage to
Equipment. Do not close the circuit
between terminals SC-SN. If you
close the circuits between terminals
SC-SP and terminals SC-SN at the
same time, it will cause damage to
the drive.
•
Sourcing Mode, Internal power supply:
Install the jumper to close the circuit
between terminals SC-SN.
NOTICE
Damage to
Equipment. Do not close the circuit
between terminals SC-SP. If you
close the circuits between terminals
SC-SP and terminals SC-SN at the
same time, it will cause damage to
the drive.
•
External power supply: Remove the
jumper from the MFDI terminals. It is
not necessary to close the circuit
between terminals SC-SP and
terminals SC-SN.
S2
MFDI selection 2
(ON: Reverse run, OFF: Stop)
S3
MFDI selection 3
(External fault (N.O.))
S4
MFDI selection 4
(Fault reset)
S5
MFDI selection 5
(Multi-step speed reference 1)
S6
MFDI selection 6
(Multi-step speed reference 2)
S7
MFDI selection 7
(Jog command)
SN
MFDI power supply 0 V
MFDI power supply, 24 V (maximum 150
mA)
NOTICE
Damage to
Equipment. Do not close the circuit
between terminals SP-SN. If you close
the circuits between terminals SC-SP
and terminals SC-SN at the same time, it
will cause damage to the drive.
SC
MFDI selection common
SP
MFDI power 24 Vdc