Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
The display units for this parameter is 0.01 A.
The value set for
E2-01
becomes the reference value for motor protection and the torque
limit. Enter the motor rated current written on the motor nameplate. Auto-Tuning the
drive will automatically set
E2-01
to the value input for
T1-04 [Motor Rated Current]
.
■
E5-03: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
Motor Rated
Current (FLA)
Sets the PM motor rated current (FLA).
Determined by
o2-04, C6-01
(10% to 200% of
the drive rated
current)
Note:
The display units for this parameter is 0.01 A.
The drive automatically sets
E5-03
to the value input for
T2-06 [PM Motor Rated
Current]
after you do these types of Auto-Tuning:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM Stationary Tuning for Stator Resistance
•
PM Rotational Auto-Tuning
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated
Current (FLA)
Sets the motor rated current in amps.
Determined by
E9-01 and o2-04
(10% to 200% of
the drive rated
current)
Note:
The display units for this parameter is 0.01 A.
The setting value of
E9-06
is the reference value for motor protection. Enter the motor
rated current written on the motor nameplate. Auto-Tuning the drive will automatically set
E9-06
to the value input for
T4-07 [Motor Rated Current]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV