L8-29: Output Unbalance Detection Sel
No.
(Hex.)
Name
Description
Default
(Range)
L8-29
(04DF)
Output Unbalance
Detection Sel
Sets the function to detect
LF2
.
1
(0, 1)
This function prevents damage to PM motors. Current unbalance can heat a PM motor and demagnetize the
magnets. When the current is unbalanced, the drive will detect
LF2
to stop the motor and prevent damage to the
motor.
0 : Disabled
1 : Enabled
■
L8-31: LF2 Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-31
(04E1)
LF2 Detection Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1
–
100)
When the output current is unbalanced for longer than the time set in
L8-31
, the drive detects
LF2
.
Note:
•
Set
L8-29 = 1 [Output Unbalance Detection Sel = Enabled]
to enable
L8-31
.
•
If the drive incorrectly detects
LF2
, increase
L8-31
in 5-unit increments.
•
The keypad shows
L8-31
when
E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)]
in EZ Vector Control.
■
L8-35: Installation Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
0
(0 - 3)
Note:
•
Parameter
A1-03 [Initialize Parameters]
does not initialize this parameter.
•
This parameter is set to the correct value when the drive is shipped. Side-by-Side installation
–
Change the value only in these conditions:
–
When you install a UL Type 1 kit on an IP20/UL Open Type drive to convert the drive to an IP20/UL Type 1 drive.
–
Mounting a standard drive with the heatsink outside the enclosure panel.
The overload protection detection level for the drive is automatically adjusted to the optimal value in accordance
with the setting value. Refer to
Derating Depending on Ambient Temperature on page 324
for information about
derating as specified by ambient temperature.
0 : IP20/UL Open Type
Use this setting to install IP20/UL Open Type drives.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive side-by-side.
2 : IP20/UL Type 1
Use this setting to install IP20/UL Type 1 or IP55 drives.
3 : External Heatsink
Use this setting when the heatsink (cooling fin) is outside the control panel.
■
L8-40: Carrier Freq Reduction Off-Delay
No.
(Hex.)
Name
Description
Default
(Range)
L8-40
(04F1)
Carrier Freq Reduction Off-
Delay
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
Determined by A1-02
(0.00 - 2.00 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...