YASKAWA
SIEPC71061753A GA500 Technical Manual
705
■
L8-09: Output Ground Fault Detection
No.
(Hex.)
Name
Description
Default
(Range)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
Determined by o2-04
(0, 1)
0 : Disabled
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect
GF
[Ground Fault]
.
Note:
If the ground path impedance is low,
oC [Overcurrent]
,
SC [Out Short Circuit or IGBT Fault]
, or
ov [DC Bus Overvoltage]
can stop the
motor.
■
L8-10: Heatsink Fan Operation Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0
(0 - 2)
0 : During Run, w/ L8-11 Off-Delay
The drive turns on the fan when a Run command is active.
1 : Always On
The fan turns on when you supply power to the drive. When you release the Run command and the delay time set
in
L8-11 [HeatsinkCoolingFan Off DelayTime]
is expired, the fan stops. his setting extends the fan lifetime.
2 : On when Drive Temp Reaches L8-64
The fan turns on when the drive detects that the main circuit is overheating.
■
L8-11: Heatsink Fan Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the
Run command when
L8-10 = 0 [Heatsink Cooling Fan Ope Select = Dur Run (OffDly)]
.
60 s
(0 - 300 s)
■
L8-12: Ambient Temperature Setting
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +60 °C)
Note:
The setting range changes when the
L8-35 [Installation Method Selection]
value changes:
•
0 [IP20/UL Open Type]
: -10 °C to +60 °C
•
1 [Side-by-Side Mounting]
: -10 °C to +50 °C
•
2 [IP20/UL Type 1]
: -10 °C to +50 °C
•
3 [External Heatsink]
: -10 °C to +50 °C
The drive automatically adjusts the drive rated current to the best value as specified by the set temperature. Set the
ambient temperature of the area where you install the drive to a value that is more than the drive rating.
Refer to
Derating Depending on Ambient Temperature on page 324
for information about derating as specified by
ambient temperature.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...