Figure 12.126 Undertorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/
undertorque detection function.
■
Mechanical Weakening Detection
The Mechanical Weakening Detection function detects the mechanical weakening of a machine that can cause
overtorque or undertorque because of motor speed and total drive operation time.
The drive activates the function if the drive total operation time is longer than the time set in
L6-11 [Mech Fatigue
Hold Off Time]
. You can use
U4-01 [Cumulative Ope Time]
to monitor the total operation time.
Parameter Settings
If overtorque or undertorque occur during the speed range set in
L6-08 [Mechanical Fatigue Detect Select]
and
L6-09 [Mech Fatigue Detect Speed Level]
for the length of time set in
L6-10 [Mech Fatigue Detect Delay Time]
,
the drive will detect Mechanical Weakening. The drive uses
L6-01 to L6-03 [Torque Detection 1 Setting
Parameter]
to detect
oL5 [Mechanical Weakening Detection 1]
or
UL5 [Mechanical Weakening Detection 2]
.
Parameter
L6-08
sets the operation after detection.
Set the terminal that outputs the fault in
H2-01 to H2-03 [MFDO Function Selection]
.
Table 12.71 Mechanical Weakening Detection Settings Parameters
Configuration Parameter
Mechanical Deterioration Detection
MFDO Function Select
•
Terminal MA-MC
•
Terminal P1-C1
•
Terminal P2-C2
H2-01, H2-02, and H2-03 = 22
Operation Selection after Detection
L6-08
Detection Start Time
L6-11
Speed Range
Detection Criteria
L6-08
Detection Level
L6-09
Detection Time
L6-10
Overtorque
Detection Criteria
L6-01
Detection Level
L6-02
Detection Time
L6-03
■
L6-01: Torque Detection Selection 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-01
(04A1)
Torque Detection Selection
1
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0
(0 - 8)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-02 [Torque
Detection Level 1]
for the length of time set in
L6-03 [Torque Detection Time 1]
. The drive detects undertorque if
the motor current or output torque is less than the level set in
L6-02
for the length the time set in
L6-03
.
0 : Disabled
The drive will not detect overtorque or undertorque.
1 : oL @ Speed Agree - Alarm only
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...