YASKAWA
SIEPC71061753A GA500 Technical Manual
545
■
d1-13: Reference 13
No.
(Hex.)
Name
Description
Default
(Range)
d1-13
(028E)
RUN
Reference 13
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 13.
■
d1-14: Reference 14
No.
(Hex.)
Name
Description
Default
(Range)
d1-14
(028F)
RUN
Reference 14
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 14.
■
d1-15: Reference 15
No.
(Hex.)
Name
Description
Default
(Range)
d1-15
(0290)
RUN
Reference 15
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 15.
■
d1-16: Reference 16
No.
(Hex.)
Name
Description
Default
(Range)
d1-16
(0291)
RUN
Reference 16
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 16.
■
d1-17: Jog Reference
No.
(Hex.)
Name
Description
Default
(Range)
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
. Set
H1-xx = 6 [MFDI Function Select = Jog Reference Selection]
to use the Jog frequency reference.
6.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...