![YASKAWA CIPR-GA50C series Technical Manual Download Page 522](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765522.webp)
522
YASKAWA
SIEPC71061753A GA500 Technical Manual
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-02: Deceleration Time 1
No.
(Hex.)
Name
Description
Default
(Range)
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-03: Acceleration Time 2
No.
(Hex.)
Name
Description
Default
(Range)
C1-03
(0202)
RUN
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-04: Deceleration Time 2
No.
(Hex.)
Name
Description
Default
(Range)
C1-04
(0203)
RUN
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-05: Acceleration Time 3
No.
(Hex.)
Name
Description
Default
(Range)
C1-05
(0204)
RUN
Acceleration Time 3
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-06: Deceleration Time 3
No.
(Hex.)
Name
Description
Default
(Range)
C1-06
(0205)
RUN
Deceleration Time 3
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
■
C1-07: Acceleration Time 4
No.
(Hex.)
Name
Description
Default
(Range)
C1-07
(0206)
RUN
Acceleration Time 4
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
Note:
When
C1-10 = 0 [Accel/Decel Time Setting Units = 0.01 s (0.00 to 600.00 s)]
, the setting range is 0.00 to 600.00 s.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...