SIEPC71061753A GA500 Technical Manual
Note:
•
To use Speed Estimation Speed Search with V/f Control, do Rotational Auto-Tuning before you set the Speed Search function. If the
wire length between the drive and motor changed since the last time you did Auto-Tuning, do Stationary Auto-Tuning for Line-to-Line
Resistance process again.
•
If
A1-02 = 5, 6 [PM Open Loop Vector, PM Advanced Open Loop Vector]
and the wiring distance between the motor and drive is long
or if the motor is coasting at more than or equal to 120 Hz, do not use Speed Search to restart the motor. Use Short Circuit Braking.
■
Current Detection 2
Use this Speed Search function with induction motors. Set
b3-24 = 2 [Speed Search Method Selection = Current
Detection 2]
. Current Detection Speed Search injects current into the motor to detect the speed of an induction
motor. Speed Search increases the output voltage for the time set in
L2-04 [Powerloss V/f Recovery Ramp Time]
,
starting from the maximum output frequency or the frequency reference.
Figure 12.22 Current Detection 2 after Momentary Power Loss
Note:
Once power is restored, the drive will not execute Speed Search until the time set in
b3-05 [Speed Search Delay Time]
has passed. Thus,
the drive will not always start Speed Search although the time set in
L2-03 [Minimum Baseblock Time]
is expired.
If you enter the Run command at the same time as Speed Search, the drive will not do Speed Search until the time
set in
L2-03
is expired. When the value set in
L2-03
<
b3-05
, the drive will use the wait time set in
b3-05
.
Figure 12.23 Speed Search Selection at Start (Current Detection Type)
WARNING!
Sudden Movement Hazard. Do not do Current Detection Speed Search with light loads or a stopped motor. If you
do Auto-Tuning in these conditions, the motor can suddenly accelerate and cause serious injury or death.
Note:
•
You cannot use Current Detection Speed Search with PM motors.
•
If the motor is rotating in reverse, you cannot do Speed Search.
•
If the drive detects
oL1 [Motor Overload]
during Current Detection Speed Search, decrease the value set in
b3-03
.
•
If the drive detects
oC [Overcurrent]
or
ov [Overvoltage]
during Current Detection Speed Search after the drive recovers from a
momentary power loss, increase the value set in
L2-03
.
■
Speed Estimation
Use this Speed Search function with induction motors. Set
b3-24 = 1 [Speed Search Method Selection = Speed
Estimation]
. This function uses less current and has a shorter search time than other functions. This function lets
you do Speed Search when the motor is rotating in reverse. When you return power after a power loss, the motor
will not suddenly accelerate.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...