486
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
b1-17: Run Command at Power Up
No.
(Hex.)
Name
Description
Default
(Range)
b1-17
(01C6)
Run Command at Power Up
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
0
(0, 1)
0 : Disregard Existing RUN Command
The drive does not start to operate the application when the power is switched ON, even when there is an existing
Run command.
Enter the Run command again to operate the application.
Note:
When you energize the drive,
on the keypad will flash quickly if the Run command is already enabled from an external source.
1 : Accept Existing RUN Command
When there is an existing Run command, the drive starts to operate the application when the power is switched
ON.
WARNING!
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you
do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate in
reverse when you energize the drive.
■
b1-35: Digital Input Deadband Time
No.
(Hex.)
Name
Description
Default
(Range)
b1-35
(1117)
Expert
Digital Input Deadband
Time
Sets the deadband time for MFDIs.
0.0 ms
(0.0 to 100.0 ms)
When the on/off time for MFDIs is longer than the time set in
b1-35
, the drive activates the MFDI. Set this
parameter to prevent malfunctions caused by relay chattering for applications in which relays send input to MFDI
terminals.
◆
b2: DC Injection Braking and Short Circuit Braking
b2 parameters
set the DC Injection Braking and Short Circuit Braking functions.
•
DC Injection Braking: A braking method that injects DC current into the motor windings. This function should
not be used too frequently, because it generates a fair amount of heat in the motor.
•
Short Circuit Braking: A braking method for PM motors.
■
b2-01: DC Injection/Zero SpeedThreshold
No.
(Hex.)
Name
Description
Default
(Range)
b2-01
(0189)
DC Injection/Zero
SpeedThreshold
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Determined by A1-02
(0.0 - 10.0 Hz)
Note:
This parameter is available when
b1-03 = 0 [Stopping Method Selection = Ramp to Stop]
.
When the control method selected in
A1-02 [Control Method Selection]
changes, the
b2-01
function changes.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...