![YASKAWA CIPR-GA50C series Technical Manual Download Page 262](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765262.webp)
262
YASKAWA
SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
CrST
Cannot Reset
The drive received a fault reset command when a
Run command was active.
Turn off the Run command then de-energize and re-energize the
drive.
Code
Name
Causes
Possible Solutions
CyC
MECHATROLINK
CommCycleSettingErr
The communications cycle setting of the controller
is not in the permitted range of the
MECHATROLINK interface option.
Set the communications cycle of the controller in the permitted
range of the MECHATROLINK interface option.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
CyPo
Cycle Power to Accept Changes
Although
F6-15 = 1 [Comm. Option Parameters
Reload = Reload Now]
, the drive does not update
the communication option parameters.
Re-energize the drive to update the communication option
parameters.
Code
Name
Causes
Possible Solutions
dEv
Speed Deviation
The load is too large.
Decrease the load.
The acceleration/deceleration times are too short.
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
The
dEv
detection level settings are incorrect.
Adjust
F1-10 [Speed Deviation Detection Level]
and
F1-11
[Speed Deviation Detect DelayTime]
.
The load is locked up.
Examine the machine.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of
F1-10
for longer than
F1-11
.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F1-04 [Speed Deviation Detection Select]
.
Code
Name
Causes
Possible Solutions
dnE
Drive Disabled
A terminal set for
H1-xx = 6A [Drive Enable]
turned OFF.
Examine the operation sequence.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
dWA2
DriveWorksEZ Alarm 2
There was an error in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
dWA3
DriveWorksEZ Alarm 3
There was an error in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
dWAL
DriveWorksEZ Alarm
There was an error in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
E5
MECHATROLINK Watchdog
Timer Err
The drive detected a watchdog circuit exception
while it received data from the controller.
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
•
MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
•
MECHATROLINK-III Installation Manual
(MECHATROLINK Members Association, publication
number MMATDEP018)
Note:
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F6-25 [MECHATROLINK Watchdog Error Sel]
.
Code
Name
Causes
Possible Solutions
EF
FWD/REV Run Command Input
Error
A forward command and a reverse command were
input at the same time for longer than 0.5 s.
Examine the forward and reverse command sequence and correct
the problem.
Note:
•
If the drive detects
EF
, the motor will ramp to stop.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...