![YASKAWA CIPR-GA50C series Technical Manual Download Page 258](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765258.webp)
258
YASKAWA
SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
When
A1-02 = 5, 6 [Control Method Selection =
OLV/PM or AOLV/PM]
, the output current is more
than the value set in
L8-27 [Overcurrent Detection
Gain]
.
Set
L8-27
correctly.
Note:
•
The drive detects this error if there is a short circuit or ground fault on the drive output side, or an IGBT failure.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
SCF
Safety Circuit Fault
The safety circuit is broken.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
SEr
Speed Search Retries Exceeded
The speed search-related parameters are set
incorrectly.
•
Decrease the value set in
b3-10 [Speed Estimation Detection
Gain]
.
•
Increase the value set in
b3-17 [Speed Est Retry Current
Level]
.
•
Increase the value set in
b3-18 [Speed Est Retry Detection
Time]
.
•
Do Auto-Tuning again.
The motor is coasting in the opposite direction of
the Run command.
Set
b3-14 = 1 [Bi-directional Speed Search = Enabled]
.
Note:
•
The drive detects this error if the number of speed search restarts is more than the value set in
b3-19 [Speed Search Restart Attempts]
.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
STPo
Motor Step-Out Detected
The motor code is set incorrectly for PM Control
Methods.
•
Set
E5-01 [PM Motor Code Selection]
correctly as specified
by the motor.
•
For specialized motors, refer to the motor test report and set
E5-xx
correctly.
The load is too large.
•
Increase the value set in
n8-55 [Motor to Load Inertia Ratio]
.
•
Increase the value set in
n8-51 [Pull-in Current @
Acceleration]
. If the drive detects
STPo
during deceleration
when increasing the value set in
n8-51
, set the value of
n8-79
[Pull-in Current @ Deceleration]
lower than
n8-51
.
•
Decrease the load.
•
Replace the drive and motor with larger capacity models.
The load inertia is too large.
Increase the value set in
n8-55
.
The acceleration/deceleration times are too short.
•
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
•
Increase the value set in
C2-01 [S-Curve Time @ Start of
Accel]
.
Speed response is too slow.
Increase the value set in
n8-55
.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
TiM
Keypad Time Not Set
There is a battery in the keypad, but the date and
time are not set.
Use the keypad to set the date and time.
Note:
•
Do a Fault Reset to clear the fault.
•
Parameter
o4-24 [bAT Detection Selection]
enables and disables
TiM
detection.
Code
Name
Causes
Possible Solutions
UL3
Undertorque Detection 1
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-02 [Torque Detection Level 1]
and
L6-03 [Torque
Detection Time 1]
settings.
Note:
•
The drive detects this error if the drive output current is less than the level set in
L6-02
for longer than
L6-03
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in
L6-01 [Torque Detection Selection 1]
.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...