A.16 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection. Changing the control mode initializes these
parameters to the values shown here.
u
A1-02 (Motor Control Mode) Dependent Parameters
Table A.3 A1-02 (Motor Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
OLV/PM (5)
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
0.00 to 6.00
0.01
0.30
C2-01
S-Curve Characteristic at Accel Start
0.00 to 10.00
0.01 s
0.20
1.00
C4-01
Torque Compensation Gain
0.00 to 2.50
0.01
1.00
0.00
C4-02
Torque Compensation Primary Delay Time
0 to 60000
1 ms
200
100
C6-02
Carrier Frequency Selection
1 to 9; A to F
1
2
E1-04
Maximum Output Frequency
40.0 to 240.0
0.1 Hz
60.0
E1-05
Maximum Voltage
0.0 to 733.1
0.1 V
200.0
E1-06
Base Frequency
0.0 to 240.0
0.1 Hz
60.0
E1-09
Minimum Output Frequency
0.0 to 240.0
0.1 Hz
3.0
L1-01
Motor Overload Protection Selection
0, 1, 4
1
1
4
L3-20
DC Bus Voltage Adjustment Gain
0.00 to 5.00
0.01
1.00
0.65
L8-38
Carrier Frequency Reduction Selection
0 to 2
1
0
L8-40
Carrier Frequency Reduction Off-Delay Time
0.00 to 2.00
0.01 s
0.50
0.00
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-03, V/f Pattern Selection.
A.16 Control Mode Dependent Parameter Default Values
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
239
A
Parameter List