B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
157
Pa
ra
me
te
r L
is
t
B
◆
U: Monitors
Monitor parameters allow the user to view regenerative unit status, fault information, and other data concerning
regenerative unit operation.
o4-03
(50EH)
Cooling Fan
Operation Time
Setting
FanElapsTimeCn
Sets the value of the fan operation time monitor U4-03 in
units of 10 h.
Default: 0
Min.: 0
Max.: 9999
o4-05
(51DH)
Capacitor
Maintenance Setting
BusCap Maint Set
Sets the value of the Maintenance Monitor for the
capacitors. See U4-05 to check when the capacitors may
need to be replaced.
Default: 0%
Min.: 0%
Max.: 150%
o4-07
(523H)
DC Bus Pre-Charge
Relay Maintenance
Setting DC Bus
Pre-Charge Relay
Maintenance Setting
ChrgCircMaintSet
Sets the value of the Maintenance Monitor for the soft
charge bypass relay.
See U4-06 to check when the bypass relay may need to be
replaced.
Default: 0%
Min.: 0%
Max.: 150%
o4-11
(510H)
U2, U3 Initialization
Fault Data Init
0: No Reset
1: Reset
0: U2-
and U3-
monitor data is not reset when the
regenerative unit is initialized (A1-03).
1: U2-
and U3-
monitor data is reset when the
regenerative unit is initialized (A1-03).
Default: 0
Min.: 0
Max.: 1
o4-12
(512H)
kWh Monitor
Initialization
kWh Monitor Init
0: No Reset
1: Reset
0: U4-10 and U4-11 monitor data is not reset when the
regenerative unit is initialized (A1-03).
1: U4-10 and U4-11 monitor data is reset when the
regenerative unit is initialized (A1-03).
Default: 0
Min.: 0
Max.: 1
o4-13
(528H)
Number of Run
Commands Counter
Initialization
Run Counter Init
0: No Reset
1: Reset
0: Number of Run commands counter is not reset when the
regenerative unit is initialized (A1-03).
1: Number of Run commands counter is reset when the
regenerative unit is initialized (A1-03).
Default: 0
Min.: 0
Max.: 1
o4-19
(113AH)
Power Unit Price
Cost per 1 kWh
This parameter is used to calculate the power rate that is
displayed for User Monitors U9-07 through U9-14.
Set the price per 1 kWh.
Default: 000.00
Min.: 000.00
Max.: 650.00
<7> Parameter is available in software versions PRG: 2003 and later.
No.
(Address
Hex)
Name
LCD
Display
Description
Analog
Output
Level
Unit
U1: Operation Status Monitors
U1-10
(49H)
Input Terminal
Status
Input Term
Sts
Displays the input terminal status.
No signal
output
available
–
No.
(Address
Hex)
Name
LCD Display
Description
Values
U1 - 10=
0 0 0 0 0 0 0 0
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1: ON 0: OFF