
152
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
Figure 1.115
Figure 120
■
P3-08 Multi Pump Setpoint Decrease
Setting Range:
0.0 to 6000.0
Factory Default: 0.0
The iQpump drive can be configured for multiplex pumping operation. The multiplex pumping operation can have the system setpoint
decreased each time a pump is staged (turned ON) by programming the amount to be decreased into the Multi Pump Setpoint Decrease
(P3-08). The system’s setpoint will be raised by this amount when each pump is de-staged (turned OFF). Refer to
below.
The units for this parameter are determined by the System Units (P1-02).
Example: Constant Pressure System
System Setpoint: 80 PSI
Pressure Transducer: 150 PSI
Multi Pump Setpoint Increase: 4 PSI
Pump 1 (Running) Setpoint = 80 PSI
Pump 1 + Pump 2 (Running) Setpoint = 76 PSI (80 PSI - 4 PSI)
Pump 1 + Pump 2 + Pump 3 (Running) Setpoint = 72 PSI (80 PSI - 4 PSI - 4 PSI)
Time
SET-POINT
Set-Point + 2 x P3-07
Set-Point + P3-07
PUMP 1
PUMP 1 + 2
PUMP 1 + 2 + 3
PUMP 1 + 2
Set-Point + P3-07
PUMP 1
Summary of Contents for CIMR-P7U-2011-107
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02 ...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK ...