o4-03
Cooling Fan
Operation
Time Setting
Sets the value of the fan operation time in units of 10
h.
0 to
9999
0
O
50E
–
o4-05
Capacitor
Maintenance
Setting
Sets the value of the capacitor maintenance time
monitor U4-05.
0 to 150
0%
O
51D
–
o4-07
DC Bus Pre-
Charge Relay
Maintenance
Setting
Sets the value of the Soft Charge Bypass Relay
Maintenance monitor U4-06.
0 to 150
0%
O
523
–
o4-09
IGBT
Maintenance
Setting
Sets the value of the IGBT Maintenance monitor
U4-07.
0 to 150
0%
O
525
–
o4-11
U2
Initialization
0: U2-
oo
monitor data are not reset when the drive
is initialized using A1-03.
1: U2-
oo
monitor data are reset when the drive is
initialized using A1-03. (The value of o4-11 is
automatically returned to 0.)
0, 1
0
O
510
–
<1>
Parameter can be changed during run.
u
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other
information about drive operation.
No.
Name
Description
Analog Output
Level
Unit Mode Addr.
Hex
U1: Operation Status Monitors
Use U1 monitors to display the operation status of the drive.
U1-01
Frequency
Reference
Monitors the frequency reference
10 V: Max
frequency
0.01
Hz
O
40
U1-02
Output
Frequency
Displays the output frequency. Display units are
determined by o1-03.
10 V: Max
frequency
0.01
Hz
O
41
U1-03
Output
Current
Displays the output current.
10 V: Drive rated
current
0.01
O
42
U1-06
Output
Voltage
Reference
Displays the output voltage.
10 V: 200 Vrms
(400 Vrms)
0.1 V
O
45
U1-07
DC Bus
Voltage
Displays the DC bus voltage.
10 V: 400 V (800
V)
1 V
O
46
B.2 Parameter Table