B.3
Defaults Determined by Drive Capacity
(o2-04) and ND/HD (C6-01)
Table B.1 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings
No.
Description
Unit
Default Settings
−
Model CIMR-J
o
−
BA0001
BA0002
BA0003
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex
30
31
32
−
Motor rated power
kW
0.1
0.2
0.2
0.4
0.4
0.75
C6-02
Carrier frequency
−
4
7
4
7
4
7
E2-01
Motor rated current
A
0.60
1.10
1.10
1.90
1.90
3.30
E2-02
Motor rated slip
Hz
2.50
2.60
2.60
2.90
2.90
2.50
E2-03
Motor no-load current
A
0.40
0.80
0.80
1.20
1.20
1.80
E2-05
Motor line-to-line resistance
Ω
35.98
20.56
20.56
9.842
9.842
5.156
−
Momentary power loss ride-
through time
s
0.1
0.1
0.1
0.1
0.1
0.1
−
Mom. power loss Baseblock
time
s
0.2
0.2
0.2
0.2
0.2
0.3
No.
Description
Unit
Default Settings
−
Model CIMR-J
o
−
BA0006
BA0010
C6-01
Normal/Heavy Duty
−
HD
HD
ND
o2-04
Drive Model Selection
Hex
33
34
C6-02
Carrier frequency
−
4
7
3
7
E2-01
Motor rated current
A
3.30
6.20
6.20
8.50
E2-02
Motor rated slip
Hz
2.50
2.60
2.60
2.90
E2-03
Motor no-load current
A
1.80
2.80
2.80
3.00
E2-05
Motor line-to-line resistance
Ω
5.156
1.997
1.997
1.601
−
Momentary power loss ride-through time
s
0.2
0.2
0.3
0.3
−
Momentary power loss Baseblock time
s
0.3
0.4
0.4
0.5
Table B.2 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD settings
No.
Description
Unit
Default Settings
−
Model CIMR-J
o
−
2A0001
2A0002
2A0004
2A0006
2A0008
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
−
96 (60H)
97 (61H)
98 (62H)
99 (63H)
100 (64H)
−
Motor rated power
kW
0.1
0.2
0.2
0.4
0.4
0.75 0.75
1.1
1.1
1.5
C6-02
Carrier frequency
−
4
7
4
7
4
7
4
7
3
7
E2-01
Motor rated current
A
0.60 1.10 1.10 1.90 1.90 3.30 3.30 4.90 4.90 6.20
E2-02
Motor rated slip
Hz
2.50 2.60 2.60 2.90 2.90 2.50 2.50 2.60 2.60 2.60
E2-03
Motor no-load current
A
0.40 0.80 0.80 1.20 1.20 1.80 1.80 2.30 2.30 2.80
E2-05
Motor line-to-line
resistance
Ω
35.98 20.56 20.56 9.842 9.842 5.156 5.156 3.577 3.577 1.997
L2-02
Momentary power loss ride-
through time
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.3
0.3
B.3 Defaults Determined by Drive Capacity (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
219
B
Parameter List
2/6/2008-14:44