10 CC-Link Code Numbers
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
47
Drive Monitor Codes
Table 30 Drive Monitor Codes
Monitor Code
Name
Comments
0000H
Reserved
–
0001H
Output frequency
Units are determined by o1-03.
0002H
Output current
Units are either 0.1 A or 0.01 A, depending on the capacity of the drive.
0003H
Output voltage reference
Units: 0.1 V
0004H
Reserved
–
0005H
Frequency reference
Units are determined by o1-03.
0006H
Motor speed
Units: 1 r/min
0007H
Motor torque
Units: 0.1%
0008H
DC bus voltage
Units: 1 V
0009H to 000DH
Reserved
–
000EH
Output power
Units: 1 V
000FH
Input terminal status
0010H
Output terminal status
• When using YASKAWA AC Drive 1000-Series
• When using YASKAWA AC Drive GA500
• When using YASKAWA AC Drive GA700 and GA800
0011H
Reserved
–
0012H
Motor excitation current
Units: 0.1%
0013H
Reserved
–
0014H
Cumulative operation time
• Units: 1 hour
• Parameter o4-02 determines if the operation time is the considered to be whenever
the drive powered on or only when there is voltage output.
0015H, 0016H
Reserved
–
0017H
Actual operation time
• Units: 1 hour
• Parameter o4-02 determines if the operation time is the considered to be whenever
the drive powered on or only when there is voltage output.
0018H
Motor secondary current
–
7
6
5
4
3
2
1
0
Multi-Function Digital Input 1 (terminal S1 enabled)
Multi-Function Digital Input 2 (terminal S2 enabled)
Multi-Function Digital Input 3 (terminal S3 enabled)
Multi-Function Digital Input 4 (terminal S4 enabled)
Multi-Function Digital Input 5 (terminal S5 enabled)
Multi-Function Digital Input 6 (terminal S6 enabled)
Multi-Function Digital Input 7 (terminal S7 enabled)
Multi-Function Digital Input 8 (terminal S8 enabled)
1: ON
RW
0: OFF
7
6
5
4
3
2
1
0
Multi-Function Digital Output (terminal M1-M2) enabled
Multi-Function Digital Output 1 (terminal P1) enabled
<1>
Multi-Function Digital Output 2 (terminal P2) enabled
<1>
Fault Contact Output (terminal MA/MB-MC) enabled
1: ON
RW
0: OFF
Not used
7
6
5
4
3
2
1
0
Multi-Function Digital Output (terminal MA/MB-MC) enabled
Multi-Function Digital Output 1 (terminal P1-C1) enabled
Multi-Function Digital Output 2 (terminal P2-C2) enabled
1: ON
RW
0: OFF
Not used
7
6
5
4
3
2
1
0
Multi-function digital output 1 (terminal M1-M2) enabled
Multi-function digital output 2 (terminal M3-M4) enabled
Multi-function digital output 3 enabled
<1>
Fault Contact Output (terminal MA/MB-MC) enabled
1: ON
RW
0: OFF
Not used