9 Troubleshooting
40
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
Alarms
Fault LED Display on Option Side
Defining Option LED States
Figure 27
Figure 27 Option LED Labels
Table 25 LED Display
Note:
If communication stops while the drive is running, check the following:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Keypad Display
Alarm Name
AEr
Station Address Error
Option is set to an address outside the allowable setting range.
Cause
Possible Solution
Alarm
(H2-
= 10)
CC-Link Option is set to an address outside
the allowable setting range.
Set F6-10 to an address within the specified range.
YES
Keypad Display
Alarm Name
CALL
Serial communication transmission error
Communication is not established.
Cause
Possible Solution
Alarm
(H2-
= 10)
Communication wiring is faulty.
• Check for wiring errors.
• Correct the wiring.
YES
An existing short circuit or communications
disconnection
Check disconnected cables and short circuits and repair as needed.
Programming error on the master side
Check communications at start-up and correct programming errors.
Communication circuitry is damaged.
• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire
drive. For instructions on replacing the control board, contact Yaskawa
or a Yaskawa representative.
Termination resistor of the MEMOBUS/
Modbus communications is not enabled.
Set DIP switch S2 to the ON position to enable the termination resistor
on a drive located at the end of a network line.
Keypad Display
Alarm Name
CyPo
Cycle Power to Active Parameters
Comm. Option Parameter Not Upgraded
Cause
Possible Solution
Alarm
(H2-
= 10)
Although F6-15 = 1 [Comm. Option
Parameters Reload = Reload Now], the drive
did not update the communication option
parameters.
Re-energize the drive to update the communication option parameters.
Note: If the option software version is not compatible or if you install an
incorrect option to the drive, it will trigger an alarm.
YES
L.RUN
Switches on when data is being received normally. Turns off when the receive data is interrupted.
SD
Lights whenever data is sent.
RD
Light whenever data is received.
L.ERR
Lights when a CRC or abort error occurs.
GA500, GA700, and GA800 Label
1000-Series Label
L.ERR
RD
L.RUN
SD