4 Option Components
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
11
Option LED Display
Defining Option LED States
Figure 5
Figure 5 Option LED Labels
Table 4 Option LED States
Setting Station Address
Set drive parameter F6-10 to a station address (Range 1 to 64) unique to the network. If set to 0, the L.ERR light will turn
on and a Station Address Error (AEr) will occur.
Name
Indication
Operating Status
Description
Color
Status
L.RUN
Green
ON
Normal operation
Receiving data normally
OFF
Timed out
• Timed out waiting to receive
• Logging onto the network
• During reset
L.ERR
Red
ON
CRC error
• CRC error
• Station address setting error (F6-10 = 0)
OFF
During communications
• Normal communications
• During reset
SD
Red
ON
Sending data
Sending data
Note:
LED may appear to flash with slower baud
rates.
OFF
No data transfer
• No data being sent
• During reset
RD
Red
ON
Detecting data received
Detecting data that was received
Note:
LED may appear to flash with slower baud
rates.
OFF
Waiting for data
• Data not yet received
• During reset
GA500, GA700, and GA800 Label
1000-Series Label
L.ERR
RD
L.RUN
SD