A1-02 (Motor 1 Control Mode) Dependent Parameters
Table A.2 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
V/f w/PG (1)
OLV (2)
CLV (3)
b2-01
DC Injection Braking Start Frequency
0.0 to 10.0
0.1 Hz
0.5
0.5
0.5
0.5
b2-04
DC Injection Braking Time at Stop
0.00 to 10.00
0.01 s
0.50
0.50
0.50
0.50
b3-01
Speed Search Selection at Start
0 to 1
–
0
1
0
1
b3-02
Speed Search Deactivation Current
0 to 200
1%
120
–
100
–
b3-14
Bi-Directional Speed Search Selection
0 to 1
1
1
0
1
1
b5-15
PID Sleep Function Start Level
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
b6-01
Dwell Reference at Start
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
b6-03
Dwell Reference at Stop
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
C1-11
Accel/Decel Time Switching Frequency
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
C2-01
S-Curve Time at Acceleration Start
0.00 to 10.00
0.01 s
0.20
0.20
0.20
0.20
C3-01
Slip Compensation Gain
0.0 to 2.5
0.1
0.0
–
1.0
1.0
C3-02
Slip Compensation Primary Delay Time
0 to 10000
1 ms
2000
–
200
–
C4-01
Torque Compensation Gain
0.00 to 2.50
0.01
1.00
1.00
1.00
–
C4-02
Torque Compensation Primary Delay Time
0 to 10000
1 ms
200
20
–
C5-01
ASR Proportional Gain 1
0.00 to 300.00
0.01
–
0.20
–
20.00
C5-02
ASR Integral Time 1
0.000 to 10.000
0.001 s
–
0.200
–
0.500
C5-03
ASR Proportional Gain 2
0.00 to 300.00
0.01
–
0.02
–
20.00
C5-04
ASR Integral Time 2
0.000 to 10.000
0.001 s
–
0.050
–
0.500
C5-06
ASR Primary Delay Time Constant
0.000 to 0.500
0.001 s
–
–
–
0.004
C5-07
ASR Gain Switching Frequency
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-01
Jump Frequency 1
0.0 to 150.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-02
Jump Frequency 2
0.0 to 150.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-03
Jump Frequency 3
0.0 to 150.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-04
Jump Frequency Width
0.0 to 20.0
0.1
1.0 Hz
1.0 Hz
1.0 Hz
1.0 Hz
d5-02
Torque Reference Delay Time
0 to 1000
1 ms
–
–
–
0
E1-04
Maximum Output Frequency
40.0 to 150.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-05
Maximum Voltage
0.0 to 510.0
0.1 V
575
575
575
E1-06
Base Frequency
0.0 to 150.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-07
Middle Output Frequency
0.0 to 150.0
0.1 Hz
3.0
3.0
3.0
3.0
E1-08
Middle Output Frequency Voltage
0.0 to 510.0
0.1 V
15.0
15.0
E1-09
Minimum Output Frequency
0.0 to 150.0
0.1 Hz
1.5
1.5
0.5
0.0
E1-10
Minimum Output Frequency Voltage
0.0 to 510.0
0.1 V
9.0
9.0
2.0
0.0
F1-01
PG 1 Pulses Per Revolution
0 to 60000
1 ppr
600
600
600
600
F1-05
PG 1 Rotation Selection
0 to 1
–
0
0
0
0
F1-09
Overspeed Detection Delay Time
0.0 to 2.0
0.1 s
–
1.0
–
0.0
L1-01
Motor Overload Protection Selection
0 to 4
–
1
1
1
1
L4-01
Speed Agreement Detection Level
0.0 to 150.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-02
Speed Agreement Detection Width
0.0 to 20.0
0.1 Hz
2.0
2.0
2.0
2.0
L4-03
Speed Agreement Detection Level (+/-)
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-04
Speed Agreement Detection Width (+/-)
0.0 to 20.0
0.1 Hz
2.0
2.0
2.0
2.0
L8-38
Carrier Frequency Reduction Selection
0 to 2
1
A.16 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
307