1.9 n: Special Adjustments
These parameters control a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control,
High Slip Braking and resistance between motor lines.
u
n1: Hunting Prevention
Hunting Prevention prevents the drive from hunting as a result of low inertia and operating with light load. Hunting often
occurs with a high carrier frequency and an output frequency below 30 Hz.
n
n1-01: Hunting Prevention Selection
Enables or disables the Hunting Prevention function.
Note:
This function is available only when using V/f Control. Disable Hunting Prevention when drive response is more important than suppressing
motor oscillation. This function may be disabled without problems in applications with high inertia loads or relatively heavy loads.
No.
Name
Setting Range
Default
n1-01
Hunting Prevention Selection
0, 1
1
Setting 0: Disabled
Setting 1: Enabled
n
n1-02: Hunting Prevention Gain Setting
Sets the gain for the Hunting Prevention Function.
No.
Name
Setting Range
Default
n1-02
Hunting Prevention Gain Setting
0.00 to 2.50
1.00
Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
• If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
• If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.
n
n1-03: Hunting Prevention Time Constant
Determines the responsiveness of the Hunting Prevention function (affects the primary delay time for Hunting Prevention).
No.
Name
Setting Range
Default
n1-03
Hunting Prevention Time Constant
0 to 500 ms
Determined by
o2-04
Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
• Increase this value for applications with a large load inertia. A higher setting leads to slower response, which can result in
oscillation at lower frequencies.
• Lower this setting if oscillation occurs at low speed.
n
n1-05: Hunting Prevention Gain while in Reverse
This parameter functions the same as n1-02, except it is used when rotating in reverse. See the explanation for n1-02.
Note:
n1-02 is enabled for forward and reverse operation when n1-05 = 0.0 ms.
No.
Name
Setting Range
Default
n1-05
Hunting Prevention Gain while in Reverse
0.00 to 2.50
0.00
u
n2: Speed Feedback Detection Control (AFR) Tuning
These parameters help achieve speed stability when a load is suddenly applied or removed.
Note:
Properly set all motor parameters or perform Auto-Tuning before making changes to the AFR parameters.
n
n2-01: AFR Gain
Sets the internal speed feedback detection control gain in the AFR.
1.9 n: Special Adjustments
158
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Summary of Contents for A1000 HHP
Page 359: ......