background image

As many components of the 

Control Panel

 conform with the 

system control

 of Windows

Ò

,

most of the description is not necessary. The description of the 

control panel 

components

relevant for operating the Touch Panel can be found in the following:

n

Set display

Via 

‘Start

 

è

 Settings

 

è

 Control Panel

 

è

 Display’

 the dialog windows for the display

properties opens. Here you can change the settings for the monitor options.

n

Calibrate touch screen

If the touch screen does not always react to a double click or not precisely recognize

the position of an entry, you can call the dialog 

Stylus

 via 

‘Start

 

è

 Settings

è

 Control Panel’

. In the register 

Double-Tap 

you can use the grid pattern to preset a

double click velocity and test this on the symbol below. Click [OK] to accept the value.

The calibration of the touch screens is completed via the register 

Calibration

 by fol-

lowing the instructions.

n

Set Ethernet parameters

The dialog field for pre-setting an Ethernet address can be found in 

‘Start

 

è

 Settings

è

 Network and Dial-up Connections’

. The default setting is address assignment via

DHCP.

n

System properties (System)

Here you receive information about the version of the current Windows

Ò

 operating

system, the memory load and sharing (alterations here are not accepted into the reg-

istry) and the copyright. The register 

Device Name

 allows you to change the device

name that is shown during Ethernet communication for instance.

Please note that changes are set back after PowerOFF-PowerON. To

store them permanently into the registry file you have to store them

explicitly. For this call ‘Start 

è

 Programs 

è

 KuK_Tools 

è

 KuK Tools’

[Store].

The dialog window where to configure the integrated MPI interface can be found under

‘Start

 

è

 Settings

 

è

 Control Panel

 

è

 MPI Configuration’

.

n

HSA

Here you set the highest MPI address (highest station address). Within a MPI network

the highest MPI address must be identical!

n

TS

With TS (this station) you set the local MPI address for the Touch Panel.

n

Baud Rate

Enter here the transfer velocity of your MPI net. The baud rate has to be identical for

every MPI participant within the network. According to the Baud Rate the network

parameters are set.

System setting (Control

Panel)

Set MPI parameters

VIPA HMI

Deployment Touch Panel

Operating system Windows

Ò

 Embedded CE 6.0 Prof. > Structure

HB160 | TP | 62K-JID0 | en | 20-20

 

33

Summary of Contents for 62K-JID0

Page 1: ...TP 62K JID0 Manual HB160 TP 62K JID0 en 20 20 VIPA HMI Touch Panel TP 610C...

Page 2: ...62K JID0_000_TP610C 3 EN 2020 YASKAWA Europe GmbH Ohmstra e 4 91074 Herzogenaurach Tel 49 9132 744 0 Fax 49 9132 744 186 Email info yaskawa eu com Internet www yaskawa eu com...

Page 3: ...r 24 3 3 Connection to a PLC system 28 3 4 Operating system Windows Embedded CE 6 0 Prof 28 3 4 1 General 28 3 4 2 Structure 30 3 5 Communication via ActiveSync 34 3 6 Integrated Server 36 3 6 1 Gener...

Page 4: ...Descriptions may be included for units which are not present at the customer site The exact scope of delivery is described in the respective purchase contract Hereby YASKAWA Europe GmbH declares that...

Page 5: ...IPA Touch Panel 62K JID0 It contains a description of the structure project engineering and deployment Product Order number as of state HW BS TP 610C 62K JID0 01 Windows CE 6 0 Prof The manual is targ...

Page 6: ...able to all personnel in the n project design department n installation department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the component...

Page 7: ...ules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices...

Page 8: ...n Windows CE 6 0 Prof n 62K JID0 CB Movicon 11 CE Standard 4096 I O bytes n Processor Xscale 1 1GHz n Work memory 256Mbyte n User memory 512Mbyte n 380Mbyte memory for user data n CF Card II and MMC...

Page 9: ...USB A USB B 2xEthernet RJ45 Switch 2 3 Structure 2 3 1 Overview 1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply 3 Display with touch sensitive area touch screen 1 Comp...

Page 10: ...ack for Ethernet communication 7 RJ45 jack for Ethernet communication 8 Slot for DC 24V voltage supply 9 Slot for CF SD MMC storage medium Please make sure that the Touch Panel always has to be suppli...

Page 11: ...115 2kBaud n Serial bus connection in 2 wire technology using half duplex mode 9 pin SubD plug n Interface is compatible to the COM interface of a PC n Logical signals as voltage levels n Point to poi...

Page 12: ...anel is an accumulator with a suitable charging circuit This accu mulator is maintenance free and does not need to be exchanged within the life span of the Touch Panel 2 3 3 Memory management The foll...

Page 13: ...slot until the impact To remove the card touch it at the pulling edge and pull On this slot you can plug storage modules of the type SD or MMC The card may be plugged and removed during runtime and i...

Page 14: ...allation depth 45mm The degrees of protection are only guaranteed when the following is observed Material thickness at the mounting cut out 1 5 6mm The deviation from the plane for the panel cut out i...

Page 15: ...tion voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14...

Page 16: ...lses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is necessary 2 6 Technical data 2 6 1 62K JID0 CB Order no 6...

Page 17: ...tor Sub D 9 pin female Serial COM1 RS232 COM1 connector Sub D 9 pin male Serial COM2 RS422 485 isolated COM2 connector Sub D 9 pin female Number of USB A interfaces 2 USB A connector USB A host Number...

Page 18: ...04 mm x 233 mm x 7 5 mm Rear panel 285 mm x 215 mm x 45 mm Installation cut out Width 287 mm Height 217 mm Minimum 1 5 mm Maximum front panel thickness 6 mm Net weight 3251 g Environmental conditions...

Page 19: ...echargeable Lithium Battery Load time for 50 buffering period 10 h Load time for 100 buffering period 48 h Accuracy max deviation per day 10 s Operating controls Touchscreen resistive Touch function S...

Page 20: ...t 0 25 A s Power loss 12 2 W Status information alarms diagnostics Supply voltage display yes Mechanical data Housing Protection type Material die cast aluminum Mounting via integrated pivoted lever P...

Page 21: ...Order no 62K JID0 CX Certifications UL certification yes KC certification VIPA HMI Hardware description Technical data 62K JID0 CX HB160 TP 62K JID0 en 20 20 21...

Page 22: ...cabinet fronts the Touch Panel requires the following front plate cutting Touch Panel W x H in mm 62K JID0 287 x 217 The fixing technique is integrated in the casing of the Touch Panel and accessible...

Page 23: ...rs to the CageClamps like this 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm test tip The picture on the left side shows the cabling step by step from top view 1 For...

Page 24: ...ouch Panel is provided by power supply the Startup Manager will be loaded At the first startup of the Startup Manager the following start screen appears n There is a button on the initial screen with...

Page 25: ...irmware images is shown which are available on the panel and connected storage media These images will be listed with create data and version number Choose your new image If the selected image is not...

Page 26: ...ollowing batch files Start VIPA Webbrowser bat Start VIPA Webserver and Browser fullscreen bat Start VIPA Webserver and Browser bat Start VIPA Webserver bat n Under Delay Time you can adjust a delay t...

Page 27: ...egistry settings for the back light the local settings and the LAN settings will be saved by Backup in Flashdisk Backup The name of the backup file is backup bkv Which settings will be saved and the s...

Page 28: ...the application courses in the PLC according to the configured processes Via dia logues configured before process values may be monitored graphically altered and eval uated 3 4 Operating system Windo...

Page 29: ...g on an object and then dragging you can move the object on the screen If no object is selected a frame is created by the dragging that selects the touched objects Characteristics with Windows Embedde...

Page 30: ...your Touch Panel like e g applications system settings file browser etc 2 Open applications For every open application a button can be found in the task bar There is no button for minimizing The switc...

Page 31: ...allows you to select one of the available software keyboards At the moment the following standard keyboards are implemented At pushed Shift key At pushed a key Please note that can exclusively be ent...

Page 32: ...re keyboard allows you to enter key entries without connecting an external keyboard As soon as an entry is required the software keyboard is automatically shown Hide Input Panel hides the keyboard aga...

Page 33: ...nment via DHCP n System properties System Here you receive information about the version of the current Windows operating system the memory load and sharing alterations here are not accepted into the...

Page 34: ...a mobile device and a PC via USB Many devel oper tools res SCADA project engineering tools use ActiveSync for the data transfer Before you can access the Touch Panel from the PC via ActiveSync you hav...

Page 35: ...ouch Panel The USB device Touch Panel is recognized and the dialog window new part nership opens 2 Choose yes for fixing a partnership and push Next 3 In the opening window de activate all synchroniza...

Page 36: ...ed in the description of the server A client is an application that uses the service of a server within a network For example a web browser is a client because at every call of a website it sends a re...

Page 37: ...on your Touch Panel 3 As soon as your Touch Panel is connected via Ethernet you may monitor the IP address data via in the taskbar 4 After you ve confirmed the pre settings start your ftp client e g W...

Page 38: ...elete and create files and directories You may also start applications Terminating an application is not possible The establishing of a Telnet connection is password protected and has the following ap...

Page 39: ...he VNC server is on delivery deactivated Due to software reasons YASKAWA does not support the VNC server function With Autostart you can select the automatic startup of the VNC server via the Startup...

Page 40: ...sources in a Microsoft network like drives and printer Here you may assign existing public directories or printer in the network to local directories or printer in the Touch Panel Condition for this i...

Page 41: ...rname guest Input net use data testserver archiv user guest The connected network drive is then available via network data at the Touch Panel The configuration of a network printer happens with the fo...

Page 42: ...the network connection to the drive archive of test server To save the settings also after power on you have to store them to the registry with START Programs KuK_Tools KuK Tools Store Terminate netwo...

Page 43: ...erent ways n Electromagnetic fields RF coupling n Magnetic fields with power frequency n Bus system n Power supply n Protected earth conductor Depending on the spreading medium lead bound or lead free...

Page 44: ...lkie n Sparking lines sparking plugs collector of electric motors welding devices In the most times it is enough to take care of some elementary rules to guarantee the EMC Please regard the following...

Page 45: ...special EMC actions Consider to wire all inductivities with erase links Please consider luminescent lamps can influence signal lines n Create a homogeneous reference potential and ground all electrica...

Page 46: ...ltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid ground loops local distant ground constructions cubicles construction and machine parts h...

Page 47: ...e groups Group A Group B Group C Group D Group A 1 2 3 4 Group B 2 1 3 4 Group C 3 3 1 4 Group D 4 4 4 1 1 The lines may be installed in common bundles or cable trusses 2 The lines have to be installe...

Page 48: ...e of the equipotential bonding conductor must not exceed 10 of the impedance of the screen where screened signal lines are connected between the dif ferent sections of the plant and the screening is c...

Page 49: ...the cover Do not connect the screen to PIN 1 of the connector In case of stationary operations it is recommended that the remove the insulation from the screened cable without cutting the screen and t...

Page 50: ...Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU These outlets must be wired to the distribution system which is also used to connect the neutra...

Page 51: ...been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabling divided into groups Power cables 230 400V and signal lines installed in separate channels or bunc...

Reviews: