No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
r1-36
DriveWorksEZ Connection
Parameter 18 (lower)
Parameter 18 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1863
—
r1-37
DriveWorksEZ Connection
Parameter 19 (upper)
Parameter 19 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1864
—
r1-38
DriveWorksEZ Connection
Parameter 19 (lower)
Parameter 19 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1865
—
r1-39
DriveWorksEZ Connection
Parameter 20 (upper)
Parameter 20 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1866
—
r1-40
DriveWorksEZ Connection
Parameter 20 (lower)
Parameter 20 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1867
—
u
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
T1-00
Motor Selection 1/2
Selects which set of motor parameters are used and set during
Auto-Tuning. If Motor 2 selection (H1-
oo
= 16) is not selected,
this parameter will not be displayed.
1: Motor 1 (sets E1-
oo
, E2-
oo
)
2: Motor 2 (sets E3-
oo
, E4-
oo
. This selection is not displayed
if motor 2 has not been selected.)
1, 2
1
A A −
700
T1-01
Auto-Tuning Mode
Selection
Selects the Auto-Tuning mode.
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control (necessary for Energy
Savings and Speed Estimation type Speed Search)
0, 2, 3
<1>
2 or 3 in
V/f
0 or 2 in
OLV
2 in
Motor 2
A A −
701
T1-02
Motor Rated Power
Sets the motor rated power in kilowatts (kW).
Note:
If motor power is given in horsepower, power in kW can be
calculated using the following formula: kW = HP x 0.746.
<2>
<3>
A A −
702
T1-03
<4>
Motor Rated Voltage Sets the motor rated voltage in volts (V).
0.0 to
255.5
200.0 V A A −
703
T1-04
Motor Rated
Current
Sets the motor rated current in amperes (A).
10 to 200%
of drive
rated
current
<3>
A A −
704
T1-05
Motor Base
Frequency
Sets the base frequency of the motor in Hertz (Hz).
0.0 to
400.0
60.0 Hz A A −
705
T1-06
Number of Motor
Poles
Sets the number of motor poles.
2 to 48
4
A A −
706
T1-07
Motor Base Speed
Sets the base speed of the motor in revolutions per minute r/min
(RPM).
0 to 24000 1750 r/
min
A A −
707
T1-11
Motor Iron Loss
Provides the iron loss for determining the Energy Saving
coefficient.
The value set to E2-10 (motor iron loss) when the power is cycled.
If T1-02 is changed, an initial value valid for the selected capacity
will be shown.
0 to 65535
14 W
A − −
70B
These values differ depending on the
motor code value and motor
parameter settings.
<1> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control, and 2 for Motor 2 control.
<2> Setting range varies depending on drive software version.
PRG: 1016 and later: 0.03 to 650.00 kW
PRG: 1015 and earlier: 0.00 to 650.00 kW
<3> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<4> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.2 Parameter Table
398
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual