No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
o4-11
U2, U3 Initialization
0: U2-
oo
and U3-
oo
monitor data are not reset when the
drive is initialized using A1-03.
1: U2-
oo
and U3-
oo
monitor data are reset when the drive
is initialized using A1-03. (The value of o4-11 is automatically
returned to 0.)
0, 1
0
A A A
510
o4-12
kWh Monitor Initialization
0: U4-10 and U4-11 monitor data are not reset when the drive
is initialized using A1-03.
1: U4-10 and U4-11 monitor data are reset when the drive is
initialized using A1-03. (The value of o4-12 is automatically
returned to 0.)
0, 1
0
A A A
512
o4-13
Number of Run Commands
Initialize Selection
0: U4-02 monitor data is not reset when the drive is initialized
using A1-03.
1: U4-02 monitor data is reset when the drive is initialized
using A1-03. (The value of o4-13 is automatically returned to
0.)
0, 1
0
A A A
528
<1> Parameter can be changed during run.
<2> Setting range is determined by drive software version.
PRG: 1016 and later: 104 to 810
PRG: 1015 and earlier: 104 to 621
<3> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<4> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330
<5> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<6> Available in drive software versions PRG: 1011 and later. Parameter o4-03 is set in 10 h units. When o4-03 = 30, the operation time for the cooling
fan will start counting from 300 hours, and monitor U4-03 will display “300 H”. Earlier software versions set o4-03 in 1 h units.
<7> Available in drive software versions PRG: 1022 and later.
u
q: DriveWorksEZ Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
q1-01 to
q6-07
DriveWorksEZ
Parameters
Reserved for DriveWorksEZ.
-
-
A A Α
-
—
u
r: DriveWorksEZ Connection Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
r1-01
DriveWorksEZ Connection
Parameter 1 (upper)
Parameter 1 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1840
—
r1-02
DriveWorksEZ Connection
Parameter 1 (lower)
Parameter 1 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1841
—
r1-03
DriveWorksEZ Connection
Parameter 2 (upper)
Parameter 2 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1842
—
r1-04
DriveWorksEZ Connection
Parameter 2 (lower)
Parameter 1 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1843
—
r1-05
DriveWorksEZ Connection
Parameter 3 (upper)
Parameter 1 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1844
—
r1-06
DriveWorksEZ Connection
Parameter 3 (lower)
Parameter 3 for connecting DriveWorksEZ (lower).
0 to
FFFFH
0
– A A
1845
—
r1-07
DriveWorksEZ Connection
Parameter 4 (upper)
Parameter 4 for connecting DriveWorksEZ (upper).
0 to
FFFFH
0
– A A
1846
—
B.2 Parameter Table
396
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual