<4> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during run.
PRG: 1018 and later: -200.0 to 200.0%
PRG: 1017 and earlier: -200.0 to 0.0%
<5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<6> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value.
<7> Parameter available in drive software versions PRG: 1011 and later.
<8> Default setting is determined by drive model.
Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00.
Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.
u
o: Operator Related Parameters
o parameters are used to set up the LED digital operator displays.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
o1: Display Settings
Use o1 parameters to configure the digital operator display.
o1-01
<1>
Drive Mode Unit Monitor
Selection
Switches the display after the power has been turned on. When
using an LED operator, pressing the up arrow key will display
the following data:
frequency reference → rotational direction → output
frequency → output current → output voltage → U1-
oo
.
(This is done by entering the 1
oo
part of U1-
oo
. Certain
monitors are not available in some control modes.)
<2>
106
A A A
500
Set to U1-06 as a default (Output Voltage
Reference).
o1-02
<1>
User Monitor Selection After
Power Up
Selects the information that is displayed when the power is
turned on.
1: Frequency Reference (U1-01)
2: Forward/Reverse
3: Output Frequency (U1-02)
4: Output Current (U1-03)
5: User Monitor (set by o1-01)
1 to 5
1
A A A
501
o1-03
Digital Operator Display
Selection
Sets the units to display the frequency reference and output
frequency.
0: Hz
1: % (100% = E1-04)
2: r/min (enter the number of motor poles into E2-04/E4-04/
E5-04)
3: User defined by parameters o1-10 and o1-11
0 to 3
0
A A A
502
o1-05
<1>
<7>
LCD Contrast Control
Sets the brightness of the optional LCD operator.
0 to 5
3
A A A
504
o1-10
Frequency Reference Setting
and User-Set Display
These settings define the display values when o1-03 is set to
3.
o1-10 sets display values when operating at the maximum
output frequency.
o1-11 sets the position of the decimal positions.
1 to 60000
<3>
A A A
520
o1-11
Frequency Reference
Setting / Decimal Display
0 to 3
<3>
A A A
521
o2: Operator Keypad Functions
Use o2 parameters to configure LED digital operator key functions.
o2-01
LO/RE Key Function
Selection
Enables/Disables the digital operator LO/RE key.
0: Disabled
1: Enabled
0, 1
1
A A A
505
o2-02
STOP Key Function
Selection
Enables/Disables the operator panel STOP key when the drive
is operated form external sources (not operator).
0: Disabled
1: Enabled
0, 1
1
A A A
506
B.2 Parameter Table
394
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual