No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f O
LV PM
E4-12
Motor 2 Iron-Core
Saturation
Coefficient 3
Set to the motor iron saturation coefficient at 130% of
magnetic flux. Automatically set during Rotational
Auto-Tuning.
1.30 to 5.00
1.30
−
A
−
342
E4-14
<14>
Motor 2 Slip
Compensation
Gain
Sets the slip compensation gain for motor 2. The function is
the same as C3-01 for motor 1.
.
0.0 to 2.5
0.0
<12>
A
A
−
341
E4-15
Torque
Compensation Gain
- Motor 2
Sets the torque compensation gain for motor 2. The function
is the same as C4-01 for motor 1.
.
1.00 to 2.50
1.00
A
A
−
341
E5: PM Motor Parameters
E5-01
<2>
Motor Code
Selection (for PM
motor)
Enter the Yaskawa motor code for the PM motor being used.
Various motor parameters are automatically set based on the
value of this parameter.
Note:
Set to FFFF when using a specialized, custom, or non-
Yaskawa motor. For all other motors:
0 0 0 0
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
All motor parameters are reinitialized to factory settings
when this parameter is set.
0000 to
FFFF
<6>
<15>
−
−
S
329
E5-02
<2>
Motor Rated
Capacity (for PM
motor)
Sets the rated capacity of the motor.
0.10 to
18.50
<4>
−
−
S
32A
E5-03
<2>
Motor Rated
Current
Sets the motor rated current in amps.
10 to 200%
of drive
rated
current
<9>
<16>
−
−
S
32B
E5-04
<2>
Motor Poles
Sets the number of motor poles.
2 to 48
<4>
−
−
S
32C
E5-05
<2>
Motor Stator
Resistance
Set the resistance for each motor phase in units of 0.001 Ω.
0.000 to
65.000
<4>
−
−
S
32D
E5-06
<2>
Motor d Axis
Inductance
Sets the d axis inductance in units of 0.01 mH.
0.00 to
300.00
<4>
−
−
S
32E
E5-07
<2>
Motor q Axis
Inductance
Sets the q axis inductance in units of 0.01 mH.
0.00 to
600.00
<4>
−
−
S
32F
E5-09
<2>
Motor Induction
Voltage Constant 1
Set the induced phase peak voltage in units of 0.1 mV (rad/
s) [electrical angle].
Set this parameter when using a Yaskawa SSR1 series PM
motor with derate torque, or a Yaskawa SST4 series motor
with constant torque.
When setting this parameter, E5-24 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to 0,
or if neither parameter is set to 0.
0.0 to
2000.0
<4>
−
−
S
331
E5-24
<2>
Motor Induction
Voltage Constant 2
Set the induced phase-to-phase rms voltage in units of 0.1
mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa SMRA Series SPM
Motor.
When setting this parameter, E5-09 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to 0,
or if neither parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0, however, then an
alarm will not be triggered when both E5-09 and E5-24 are
set to 0.
<17>
<4>
−
−
S
353
E5-39
<18>
Current Detection
Delay Time
Sets the current detection delay time at the time of d-Axis
and q-Axis current feedback calculation.
Changing this parameter from the default setting is not
normally required.
-1000 to
1000
0 µs
A
A
A
5E2
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.2 Parameter Table
370