No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
d1-07
<1>
Frequency Reference 7
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3" (H1-
oo
= 4 and 5) are on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
286
d1-08
<1>
Frequency Reference 8
Frequency reference when multi-function input "Multi-Step
speed reference 1, 2, 3" (H1-
oo
= 3, 4, 5) are on.
0.00
Hz
A A A
287
d1-09
<1>
Frequency Reference 9
Frequency reference when multi-function input "Multi-Step
Speed Reference 4" (H1-
oo
= 32) is on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
288
d1-10
<1>
Frequency Reference 10
Frequency reference when digital input "Multi-Step Speed
Reference 1, 4" (H1-
oo
= 3 and 32) are on.
0.00
Hz
A A A
28B
d1-11
<1>
Frequency Reference 11
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 4" (H1-
oo
= 4 and 32) are on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
28C
d1-12
<1>
Frequency Reference 12
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2, 4" (H1-
oo
= 3, 4, 32) are on.
0.00
Hz
A A A
28D
d1-13
<1>
Frequency Reference 13
Frequency reference when digital inputs "Multi-Step Speed
Reference 3, 4" (H1-
oo
= 5 and 32) are on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
28E
d1-14
<1>
Frequency Reference 14
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3, 4" (H1-
oo
= 3, 5, 32) are on.
0.00
Hz
A A A
28F
d1-15
<1>
Frequency Reference 15
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3, 4" (H1-
oo
= 4, 5, 32) are on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
290
d1-16
<1>
Frequency Reference 16
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2, 3, 4" (H1-
oo
= 3, 4, 5, 32) are on.
0.00
Hz
A A A
291
d1-17
<1>
Jog Frequency Reference
Frequency reference when digital inputs "Jog Frequency
Reference", "Forward Jog", or "Reverse Jog." are on. "Jog
Frequency Reference" has priority over "Multi-Step Speed
Reference 1 to 16”.
0.00 to
400.00 Hz
<2>
<3>
6.00
Hz
S
S
S
292
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
d2-01
Frequency Reference
Upper Limit
Sets the frequency reference upper limit as a percentage of
maximum output frequency (E1-04). Output speed is limited to
this value even if the frequency reference is higher. This limit
applies to all frequency reference sources.
0.0 to
110.0
100.0
%
A A A
289
d2-02
Frequency Reference
Lower Limit
Sets the frequency reference lower limit as a percentage of
maximum output frequency (E1-04). Output speed is limited to
this value even if the frequency reference is lower. This limit
applies to all frequency reference sources.
0.0 to
110.0
0.0% A A A
28A
d2-03
Master Speed Reference
Lower Limit
Sets the minimum frequency reference lower limit if the
frequency reference is input using an analog input. Set as a
percentage of maximum output frequency (E1-04). The higher
of both values d2-02 and d2-03 will be the lower limit.
0.0 to
110.0
0.0% A A A
293
d3: Jump Frequency
Use d3 parameters to configure the drive Jump Frequency settings.
d3-01
Jump Frequency 1
d3-01 to d3-04 allow programming of three prohibited frequency
reference points for eliminating problems with resonant
vibration of the motor / machine. This feature does not eliminate
the selected frequency values, but accelerates and decelerates the
motor through the prohibited bandwidth.
The parameters must be according to the rule
d3-01 ≥ d3-02 ≥ d3-03.
0.0 to
400.0
0.0
Hz
A A A
294
d3-02
Jump Frequency 2
0.0
Hz
A A A
295
d3-03
Jump Frequency 3
0.0
Hz
A A A
296
d3-04
Jump Frequency Width
This parameter sets the dead-band width around each selected
prohibited frequency reference point. The bandwidth becomes
the designated Jump frequency, plus or minus d3-04.
0.0 to 20.0 1.0
Hz
A A A
297
d4: Frequency Reference Hold
Use d4 parameters to configure the drive frequency reference hold function.
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
365
B
Parameter List