A.3 Three-Phase 400 V Class Drives
Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload
capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).
Table A.4 Power Ratings
Item
Specification
Three-Phase Model
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
Maximum Applicable Motor
Capacity (HP)
<1>
ND Rating
0.5
0.75/1.0
1.5/2.0
3.0
3.0
5.0
HD Rating
0.5
0.75
1.0/1.5/2.0
3.0
3.0
3.0
Input
Input Current
(A)
<2>
ND Rating
1.2
2.1
4.3
5.9
8.1
9.4
HD Rating
1.2
1.8
3.2
4.4
6.0
8.2
Output
Output Current
(kVA)
<3>
ND Rating
<4>
0.9
1.6
3.1
4.1
5.3
6.7
HD Rating
<5>
0.9
1.4
2.6
3.7
4.2
5.5
Output Current
(A)
ND Rating
<4>
1.2
2.1
4.1
5.4
6.9
8.8
HD Rating
<5>
1.2
1.8
3.4
4.8
5.5
7.2
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: 380 to 480 V (proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V
<6>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective Actions
DC Link Choke
Optional
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the
motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 460 V.
<4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency.
<5> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency.
<6> DC is not available for UL standards.