1.2 Model Number and Nameplate Check
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage.
If the drive appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the drive does not function properly, contact your supplier.
u
Nameplate
IND.CONT.EQ.
7J48
PASS
:
: AC3PH 200-240V 50 / 60Hz 2.7A / 1.4A
: AC3PH 0-240V 0-400Hz 1.2A / 0.8A
: 0.6 kg
:
:
: E131457 IP20
MODEL
MAX APPLI. MOTOR : 0.75kW / 0.4kW REV : A
INPUT
OUTPUT
MASS
O / N
S / N
FILE NO
J
I
H
G
E
B
A
YASKAWA ELECTRIC CORPORATION MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
D
F
C
A – Normal Duty Amps / Heavy Duty
Amps
B – Software version
C – CE and TÜV Certification
D – Enclosure type
E – Address
<1>
F – Serial number
G – Lot number
H – Output specifications
I – Input specifications
J – AC drive model
Figure 1.1 Nameplate Information Example
<1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate.
CIMR - V U 2 A 0001 F A A
Drive
V1000
Series
No.
Customized
Specifications
A Standard model
Design
Revision
Order
No.
Region
Code
No.
Voltage Class
B
1-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 200-240 Vac
2
4
U
USA
<1> Refer to manual TOBPC71060635 for more information on these models.
<2> Refer to manual TOBPC71060621 for more information on these models.
<3> Drives with these specifications do not guarantee complete protection for the specified environmental condition.
No.
Environmental
Specification <3>
A
M
S
Standard
Humidity- and
dust-resistant
Vibration-resistant
No. Enclosure Type
IP00/Open-Chassis
B
A
IP20/Open-Chassis
F
IP20/NEMA Type 1
J
IP20/Finless <2>
L
IP00/Finless <2>
NEMA 4X/IP66 <1>
G
Refer to the tables below.
n
Single-Phase 200 V Class
Model
Normal Duty
Heavy Duty
Max. Motor Capacity kW Rated Output Current A Max. Motor Capacity kW Rated Output Current A
BA0001
0.2
1.2
0.1
0.8
BA0002
0.4
1.9
0.2
1.6
BA0003
0.75
3.3
0.4
3.0
BA0006
1.1
6.0
0.75
5.0
BA0010
2.2
9.6
1.5
8.0
BA0012
3.0
12.0
2.2
11.0
1.2 Model Number and Nameplate Check
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
25
1
Receiving