Status
Description
Open
Output frequency or frequency reference are outside the range of L4-01 ± L4-02.
Closed
Output frequency and the frequency reference are both within the range of L4-01 ± L4-02.
Note:
The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Output
frequency
User Set
Speed Agree 1
OFF
ON
Frequency
reference
OFF
ON
Frequency
reference
Output
frequency
L4-01
+/- L4-02
L4-01
+/- L4-02
Figure 5.58 User Set Speed Agree 1 Time Chart
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227
for details on setting the detection
width.
Setting 4: Frequency Detection 1
Output is closed as long as the output frequency is below the detection level set in L4-01 plus the hysteresis set in L4-02. It
closes when the output frequency falls below L4-01.
Status
Description
Open
Output frequency exceeded L4-01 + L4-02.
Closed
Output frequency is below L4-01 or has not exceeded L4-01 + L4-02.
Note:
The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Output
frequency
L4-02
Frequency
Detection 1 <1>
ON
OFF
L4-02
L4-01
L4-01
Figure 5.59 Frequency Detection 1 Time Chart
<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default
setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock.
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227
for details on setting the detection
width.
Setting 5: Frequency Detection 2
Output closes whenever the output frequency is equal to or above the detection level set in L4-01. The output opens when the
output frequency falls below L4-01 minus the hysteresis set in L4-02.
Status
Description
Open
Output frequency is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output frequency exceeded L4-01.
Note:
The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
197
5
Parameter Details