![Yamatake SDC35 User Manual Download Page 92](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228092.webp)
■
RSP input range low limit/high limit
The scaling of the RSP input can be set.
• When the model provides the RSP input, the display and setting can be
performed.
• The following shows the relationship between the RSP input and RSP based on
the range low limit and high limit settings.
■
RSP ratio and RSP bias
The RSP ratio and RSP bias can be set to correct the RSP.
• When the model provides the RSP input, the display and setting can be
performed.
• Details of RSP ratio and RSP bias calculation
Assuming that the calculation input is RSP
in
, the calculation result is RSP
out
, the
RSP ratio is RA2, and the RSP bias is BI2, the following calculation formula is
obtained.
RSP
out
= (RSP
in
X RA2) + BI2
5-34
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
RSP input range low limit
(Setup bank)
-1999 to +9999 (No decimal point)
-199.9 to +999.9 (1 digit after the decimal
point)
-19.99 to +99.99 (2 digits after the decimal
point)
-1.999 to +9.999 (3 digits after the decimal
point)
The decimal point position is the same as that
of the PV.
0U
Basic,
Standard,
High function
RSP input range high limit
(Setup bank)
1000U
Item (Bank)
Display
Contents
Initial value
User level
RSP ratio
(Parameter bank)
0.001 to 9.999
1.000
High function
RSP bias
(Parameter bank)
0U
-1999 to +9999U
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......