![Yamatake SDC35 User Manual Download Page 68](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228068.webp)
5-10
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 2
Mode
It is possible to set the AUTO/MANUAL mode selection, RUN/READY mode selection, LSP/RSP mode
selection, Auto Tuning (AT) stop/start selection, release all digital output (DO) latches, and OFF/ON selection of
communication digital input 1 (communication DI 1).
■
AUTO/MANUAL mode
The AUTO/MANUAL mode selection can be set.
• When the AUTO/MANUAL mode is changed, the display is automatically
returned to the operation display.
• If the operation type of internal contacts 1 to 5 is set at “AUTO/MANUAL”, [A--
M: AUTO/MANUAL] can be displayed, but the setting cannot be configured.
• When [CtrL: Control method] is set at "0" (ON/OFF control), [A--M:
AUTO/MANUAL] cannot be displayed and set.
• When [bit 0: AUTO/MANUAL display] of [C73: MODE display setup] is set at
"0" (no display), [A--M: AUTO/MANUAL] cannot be displayed and set.
■
RUN/READY mode
The RUN/READY mode selection can be set.
• If the operation type of internal contacts 1 to 5 is set at “RUN/READY”, [r--r:
RUN/READY] can be displayed, but the setting cannot be configured.
• When [bit 1: RUN/READY display] of [C73: MODE display setup] is set at "0"
(no display), [r--r: RUN/READY] cannot be displayed and set.
■
LSP/RSP mode
The LSP/RSP mode selection can be set.
• If the operation type of internal contacts 1 to 5 is set at “LSP/RSP”, [L--r:
LSP/RSP] can be displayed, but the setting cannot be configured.
• When [bit 2: LSP/RSP display] of [C73: MODE display setup] is set at "0" (no
display), [L--r: LSP/RSP] cannot be displayed and set.
• If the model does not have the RSP mode, [L--r: LSP/RSP] cannot be displayed
and set.
Item (Bank)
Display
Contents
Initial value
User level
AUTO/MANUAL
(Mode bank)
AUto: AUTO mode [Communication value is
"0".]
MAn: MANUAL mode [Communication value
is "1".]
AUto
Basic,
Standard,
High function
Item (Bank)
Display
Contents
Initial value
User level
RUN/READY
(Mode bank)
rUn: RUN mode [Communication value is "0".]
rdy: READY mode [Communication value is
"1".]
rUn
Basic,
Standard,
High function
Item (Bank)
Display
Contents
Initial value
User level
LSP/RSP
(Mode bank)
LSP: LSP mode [Communication value is "0".]
RSP: RSP mode [Communication value is
"1".]
LSP
Basic,
Standard,
High function
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......