Terminal assignment label symbols
The following table shows the meanings of the symbols used for the terminal
assignment label attached to the side panel of this unit:
■
Wiring Precautions
• Before starting the wiring work, carefully check the label on the side panel of this
unit to understand the model No. and terminal No. to carry out the wiring
properly.
• Use an appropriate crimp type terminal lug suitable for the M3 screw to connect
the terminals. The tightening torque of the terminal screw must be 0.4 to 0.6N·m
or less.
• Pay special attention so that no crimp type terminal lugs are in touch with
adjacent terminals.
• Keep the input/output signal cables 50cm or more away from the drive power
cable and/or power cable. Additionally, do not lay the input/output signal cables
and the drive power cable and/or power cable together in the same conduit or
duct.
• When connecting this unit and other measuring instrument in parallel, carefully
check the conditions necessary for other instrument before starting the
instrumentation.
• The digital input is so designed that it is potential free input. A contact for micro
current must be used.
• The heater current carrying conductor must be routed through the current
transformer. Additionally, carefully check that the heater current does not
exceed the allowable current limit stated in the specification. If the heater
current exceeds the allowable current limit, this might cause damage to this unit.
• The input of the current transformer cannot be used for the phase angle control.
• An optional terminal cover is available to prevent electric shock. (Model No.:
81446912-001 for
C35
or 81446913-001 for
C36
)
• The part between the control output 1 and control output 2 is not isolated. When
necessary, use an appropriate isolator.
Terminating resistor
•
Do not connect any terminating resistor in the RS-485 communication
path. Doing so might cause the communication failure.
IMPORTANT
Chapter 4. WIRING
Symbol
Contents
~
AC
DC power supply
Caution, Electric shock hazard
Caution
Terminal cover
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......