![Yamatake SDC35 User Manual Download Page 209](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228209.webp)
7-7
■
Continuous data write command (WS command)
This command writes data to continuous addresses.
●
Send message
The figure below shows the structure of the application layer of the send message
for the data write command.
●
Response message
The figure below shows the structure of the application layer of the response
message for the data write command.
●
Maximum number of write data per message
Up to 16 words for both RAM and EEPROM areas
Chapter 7. CPL COMMUNICATION FUNCTION
(2)
(1) (3) (4)
(1) Write command
(2) Data delimiter
(3) Start write data address
(4) Write data (first word)
(5) Write data (second word)
W
0
S
,
1
5
1
W
,
1
(2)
,
6
5
(2) (5)
0
• Normal termination
0
• Abnormal termination or warning
X X
The abnormal termination code is entered at XX.
For details of codes, refer to;
7-6, List of Termination Codes (on page 7-14).
(1)
(1)
(1) Termination code
Summary of Contents for SDC35